2.4 PROFIBUS-PA connection

Connect the bus cable as shown in the figure.

Connect cable cores to terminals 4 and 4.1.

Polarity reversal will not have any effect.

The cable shield should be connected with
minimum length to the ground PE.

The equipotential bonding conductor must be
connected to the device, if necessary via the
outer U-clamp ground terminal.

Power

Supply

Fieldbus

Current

Output

PROFIBUS-PA with Current Output

4-20mA

U=8-30V

+

-

Shield

PROFIBUS-

PA

5

6

4 4.1 4.2

11 12

PE

3. Menu settings for PROFIBUS-PA

For a detailed description please check the Installation and Operating Instructions manual of the device. The
following settings need to be made for operation of the BM 100 A on a PROFIBUS-PA network. Note that the service
“set slave address” is not being supported. Therefore the address can only be set by way of the local display and
operator interface.

Function (Fct.)

Input range

Description

1.6.1 BAUDRATE

Select

19200 Bd.

This is the baudrate of the internal communication interface of the device
(not PROFIBUS-PA). The value must not be changed.

1.6.2 ADDRESS

Input

0 ... 126

Settings out of the range will be ignored. If out of range 126 will be used as
default value.
Address can be changed via local display or via Profibus.

The Profibus address can be changed via the Profibus service “Set_Slave_Address”. The input range is 0...125
according to the Profibus specification. Address 126 is the default address and cannot be set via Profibus.

4. Technical data

, PROFIBUS Ident-No. EE01

Hardware
Physical

to IEC 61158-2 and the FISCO model

Bus characteristics

9... 30 V; 0.3 A max. ; 4.2 W max.

Base current

10 mA

FDE

yes: separate fault disconnection electronics
provided

Fault current

6 mA; (fault current = max. continuous
current – base current)

Starting current

lower than base current

”Ex” approval

EEx ia IIC T6 or EEx ib IIC/IIB T6 in
conformity with the FISCO model

Connection

independent of polarity

Software
GSD

all KROHNE GSD files supplied on diskette

Device profile

complete implementation of Profile B, V2.0

Functional blocks level [m], distance [m], in addition volume [m

3

]

as cyclic value plus status
mentioned units are default units

Address range

0-126, default 126,
“set slave address” not supported

Operator control

local display and operator interface at device

SAP`s

1; typically the number of service access points
is equal to the number of class 2 masters
(operating tools) which can be operated
simultaneously