Figure 2: Connection of IFM 4042 K-EEx in 2-wire mode.

The entity parameters of the "EEx i" approved transmitter power supply, including the cable
capacitances and inductances, must fit the entity parameters of the IFM 4042 K-EEx
compact flowmeter, namely Uo

30 V, Io

100 mA. Suitable HART compatible transmitter

power supplies that can be used in combination of the Altoflux 2W IFM 4042 K-EEx are:

Phoenix PI/Ex-ME-RPSS-I/I;

CEAG 6/420.

Figure 3: Connection of IFM 4042 K-EEx.

IFM 4042 K-EEx

(MGM 4042 K-EEx)

I

I

HTT

4-20 mA

4-20 mA

Transmitter Power

Supply (EEx i)

Vs

Hazardous Area

Process/

Display Unit

Safe Area

IFM 4042 K-EEx

(MGM 4042 K-EEx)

I

I

HTT

4-20 mA

4-20 mA

Transmitter Power

Supply (EEx i)

Vs

Hazardous Area

Process/

Display Unit

Safe Area

22 mA

1L=

0L=

+

_

Zener Barrier

External

Power Supply