9 Technical

data

See also the standard Installation and operating instructions.
Rated pressure

See typeplate

Ambient temperature:

-20..40/50/60

°

C, see Certificate of Conformity (1. Amendment) or

following table.

Medium temperature:

See Certificate of Conformity (1. Amendment) or following table.

Max. ambient temperature

[

°

C]

Temperature class

Max. Medium temperature

[

°

C]

40

T6
T5
T4
T3

60
75

115
155

50

T6
T5
T4
T3

50
75

115
135

60

T6
T5
T4
T3

not possible

75
75
75

Note:
The maximum medium temperatures listed in the table above are safety-technical limits! Due to
function-technical reasons (e.g. kind of liner in the measuring tube) lower limits may prevail.

10 Maintenance

The IFM 5080 K / i- EEx compact flowmeters are maintenance free with regard to flowmetering
properties. Within the scope of the periodic inspections required for electrical apparatus in
hazardous areas, it is recommended to check the flameproof enclosures for external damage and
signs of corrosion.
Opening of the housing of the primary head (coil housing) is not allowed, as this will nullify the
used type of protection for the explosion safety. There are also no serviceable parts inside the
primary head.