beautypg.com

Single channel architecture (1oo1d) – KROHNE OPTISWITCH 3x00C Relay SIL EN User Manual

Page 9

background image

For a higher average temperature of 60 °C (140 °F), the failure
rates should be multiplied by a factor of 2.5. A similar factor
applies if frequent temperature fluctuations are expected.

The calculations are also based on the specifications stated in
chapter "Planning".

After 8 to 12 years, the failure rates of the electronic
components will increase, whereby the derived PFD and PFH
values will deteriorate (IEC 61508-2, 7.4.7.4, note 3).

Overflow protection

(max. operation)

Dry run protection

(min. operation)

λ

sd

0 FIT

0 FIT

λ

su

586 FIT

565 FIT

λ

dd

124 FIT

135 FIT

λ

du

27 FIT

37 FIT

DC

S

0 %

0 %

DC

D

82 %

78 %

MTBF = MTTF + MTTR

1.33 x 10

6

h

1.33 x 10

6

h

Diagnosis test period

<

100 sek.

Single channel architecture (1oo1D)

SIL

SIL

2

HFT

0

Sensor type

Type B

Overflow protection

(max. operation)

Dry run protection

(min. operation)

SFF

96 %

95 %

PFD

avg

T

Proof

=

1 year

T

Proof

=

5 years

T

Proof

=

10 years

<

0.012 x 10

-2

<

0.059 x 10

-2

<

0.118 x 10

-2

<

0.016 x 10

-2

<

0.082 x 10

-2

<

0.164 x 10

-2

PFH

<

0.027 x 10

-6

/h

<

0.037 x 10

-6

/h

Service life

Failure rates

Fault reaction time

Specific characteristics

OPTISWITCH series 3000 • - Relay (DPDT)

9

Functional safety

32743

-

EN

-

080414