Single channel architecture (1oo1d) – KROHNE OPTISWITCH 3x00C Contactless SIL EN User Manual
Page 9
For a higher average temperature of 60 °C (140 °F), the failure
rates should be multiplied by a factor of 2.5. A similar factor
applies if frequent temperature fluctuations are expected.
The calculations are also based on the specifications stated in
chapter "Planning".
After 8 to 12 years, the failure rates of the electronic
components will increase, whereby the derived PFD and PFH
values will deteriorate (IEC 61508-2, 7.4.7.4, note 3).
Overflow protection
(max. operation)
Dry run protection
(min. operation)
λ
sd
0 FIT
0 FIT
λ
su
506 FIT
481 FIT
λ
dd
124 FIT
135 FIT
λ
du
41 FIT
56 FIT
DC
S
0 %
0 %
DC
D
75 %
71 %
MTBF = MTTF + MTTR
1.45 x 10
6
h
1.45 x 10
6
h
Diagnosis test period
<
100 sek.
Single channel architecture (1oo1D)
SIL
SIL
2
HFT
0
Sensor type
Type B
Overflow protection
(max. operation)
Dry run protection
(min. operation)
SFF
94 %
92 %
PFD
avg
T
Proof
=
1 year
T
Proof
=
5 years
T
Proof
=
10 years
<
0.018 x 10
-2
<
0.089 x 10
-2
<
0.178 x 10
-2
<
0.024 x 10
-2
<
0.122 x 10
-2
<
0.243 x 10
-2
PFH
<
0.041 x 10
-6
/h
<
0.056 x 10
-6
/h
Service life
Failure rates
Fault reaction time
Specific characteristics
OPTISWITCH series 3000 • - contactless electronic switch
9