With the potentiometer you can adapt the switching point to the

solid. It is already preset and must only be modified in special

cases.
By default, the potentiometer of OPTISWITCH 3200 C is set to

the right stop (>0.02 g/cm³ or >0.0008 lbs/in³). In case of very

light-weight solids, turn the potentiometer to the left stop

(>0.008 g/cm³ or >0.0003 lbs/in³). OPTISWITCH 3200 C will

thus be more sensitive and can detect light-weight solids more

reliably.
For instruments detecting solids in water, these values are not

applicable. The potentiometer is preset and must not be

changed.

With the mode adjustment (min./max.) you can change the

switching condition of the relay. You can set the required mode

acc. to the "Function chart" (max. - max. detection or overfill

protection, min. - min. detection or dry run protection).
We recommend connecting according to the quiescent current

principle (replay contact deenergizes when reaching the

switching point), because the relay takes on the same (safe)

condition if a failure is detected.

Control lamp for indication of the switching condition.

l

green = relay energized

l

red = relay deenergized

l

red (flashing) = failure

6.3 Function chart

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Level

Switching sta-

tus

Control lamp

Mode max.

Overfill protection

5

3

4

(8)

(6) (7)

Relay energized

Green

Mode max.

Overfill protection

5

3

4

(8)

(6) (7)

Relay deener-

gized

red

Switching point adaptation (1)

Mode adjustment (2)

Signal lamp (5)

OPTISWITCH 3200 C - with relay output

21