3 function chart – KROHNE OPTISWITCH 3000C Transistor EN User Manual

Page 18

background image

required mode acc. to the "Function chart" (max. - max.

detection or overfill protection, min. - min. detection or dry run

protection).
We recommend connecting according to the quiescent current

principle (transistor blocks when the switching point is

reached) because the transistor output takes on the same

(safe) condition if a failure is detected.

Control lamp for indication of the switching condition.

l

green = output conducts

l

red = output blocks

l

red (flashing) = failure

6.3 Function chart

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Level

Switching sta-

tus

Control lamp

Mode max.

Overfill protection

transistor con-

ducts

Green

Mode max.

Overfill protection

transistor blocks

red

Mode min.

Dry run protection

transistor con-

ducts

Green

Mode min.

Dry run protection

transistor blocks

red

Failure of the

supply voltage

(min./max. mode)

any

transistor blocks

Signal lamp (4)

18

OPTISWITCH 3000 C - with transistor output

Set up

30060

-EN
-060830