2.8 Electrical data

BW25/.././M9./../

BW25/.././M9./../

BW25/.././M9./../

BW25/.././M9./..//..

/..

/..

/..

The electronic signal output ESK and the limit switch may only be connected to intrinsically safe
circuits.

Maximum values shall be maintained for the isolated circuits and the following
reactances shall be taken into consideration:

BW25/.././M10

BW25/.././M10

BW25/.././M10

BW25/.././M10

Circuit

U

i

I

i

P

i

C

i

L

i

ESK2A

30 VDC

100mA

1W

≈20 nF

≈0 μH

ESK3-PA

24 VDC

FISCO- Field Device

SC3,5-N0-Y..

16 VDC

25mA

64mW

150nF

150 μH

I7S23,5-N...

SJ3.5-SN

16 VDC

25mA

64mW

30nF

100 μH

SJ3.5-S1N

When connecting the I/O interfaces for BW25/.././M10 liquid level indicators, the following data
shall be taken into account:
Only for connection to circuits with "protected extra-low voltage (PELV)" .
For nominal values I/O function and nominal values of the non-certified slave see BW25
handbook.