beautypg.com

4 setup procedure – KROHNE OPTISOUND 3020C 4wire EN User Manual

Page 26

background image

6.4 Setup procedure

In HART-Multidrop mode (several sensors on one input) the

address must be set before continuing with the parameter

adjustment. You will find a detailed description in the operating

instructions manual of the indicating/adjustment module.

HART mode

Standard

Address 0

Because OPTISOUND 3020 C is a distance measuring

instrument, its primary task is to measure the distance from the

sensor to the product surface. In order to indicate the actual

filling level, the measured distance must be allocated to a

specific height percentage. To make this adjustment, the full

and empty distances in the vessel are entered. If these values

are not known, it is also possible to carry out the adjustment

with other distances, e.g. 10 % and 90 %. The origin of these

distance values is always the lower edge of the flange (with

flange versions) or the lower edge of the transducer (all other

versions).
The actual level is then calculated on the basis of these

entered values. At the same time, the operating range of the

sensor is limited from maximum range to the requested range.
The real product level during this adjustment is not important,

because the min./max. adjustment is always carried out

without changing the product level. These settings can be

made ahead of time without the instrument having to be

installed.
In the main menu item "Basic adjustment", the individual

submenu items should be selected one after the other and

provided with the correct parameter values.
Start your parameter adjustment with the following menu items

of the basic adjustment:

Proceed as follows:
1 Move from the measured value display to the main menu

by pushing [OK].

Address setting HART-Multi-

drop

Parameter adjustment

Carrying out min. adjustment

26

OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire

Setup with the indicating/adjustment module

30508

-EN
-050914