PRODUCT REPAIR

The IR-700 is partially field repairable. Follow the IR-700 instruction manual for proper guidance in executing the
allowable field repair/replacement actions. No firmware changes are permitted or authorized. All failures detected by the
transmitter diagnostics or by the Proof Test must be reported.

17

OPERATING, ENVIRONMENTAL, AND PERFORMANCE SPECIFICATIONS

The Safety-Certified IR-700 product versions fully comply with, and must be operated in accordance with the functional,
environmental, and performance specifications provided in the IR-700 instruction manual. A 24 hour mean time to repair
should be assumed for safety availability calculations. All IR-700 diagnostics have a maximum 2 hour test interval.

18

SPARE PARTS

Refer to “Spare Parts” in the IR-700 instruction manual. Safety Certification is based on having a sufficient number of
spares to achieve a 24 hour mean time to repair.

19

CERTIFICATION AND FAILURE RATE DATA

All Safety-Certified IR-700 models are certified compliant to:

IEC61508:2010
SIL 2 Certified
PFDavg @ 1 year is 5.0% of the SIL2 range.
Safe Failure Fraction (SFF):

93.2%

Safety Accuracy:

+/-20% FS Range

Safety Response Time for % LEL Methane:

< 60 seconds to T90

Product Life:

10 years, based on manufacturer data.

20

CERTIFICATIONS

cCSAus, ATEX, CE Marking (Refer to the Model IR-700 Instruction Manual for details).

FMEDA Report available.

For complete information regarding performance, installation, operation, maintenance and specifications of Model IR-
700, refer to the instruction manual Document #3169.

21

REVISION LOG

Revision

Date

Changes made

Approval

1.0

7/10/13

Initial Release

RJM

2.0

8/20/13

Changed diagnostic time to 2 hours, added requirement for
minimum load on 4-20mA output

RJM

3.0

8/27/13

Removed reference to DM-700 in section 8

RJM

4.0

8/28/13

Removed redundant fault monitoring constraint

RJM