programmed to send the current output to a specified failure state (0 mA) upon internal detection of a failure. A Modbus
RS485 serial output is available in addition to the analog signal output. The Safety Certification for the TP-700 Gas
Detector only covers the use of the standard analog 4-20 mA output.

Safety-Certification of the TP-700 includes:

The 4-20 mA output

The RS-485 Modbus signal output is not part of the SIL Certification.

Note:

Proper analog signal loop resistance must be installed as documented in the instruction manual to enable proper

4-20 mA signal function. The end user must perform span calibration after any significant configuration changes or
repair events. These include: restore defaults, change of range, replacing plug-in MOS H2S sensor, and replacing ITM
module.

4

VALID INPUT RANGE

TP-700 fault annunciation is provided on the 4-20mA signal output loop by signaling to 0mA current output level for at
least 5 seconds. The receiving device must be programmed to indicate a over-range condition when current levels reach
overcurrent (>21 mA) or undercurrent (0 mA).

Note:

The TP-700 analog signal output is not safety-rated during detector warm-up, configuration mode, calibration

mode, and during signal output loop testing. Alternative means should be used at the jobsite to ensure facility safety
during these activities.

5

DIAGNOSTIC RESPONSE TIME

The TP-700 will perform all critical diagnostic functions within 1 hour. This is the worst case diagnostic detection time.

6

CERTIFICATION

The TP-700 Safety-Certified version is certified by Exida® to IEC 61508 for single input use in low and high demand,
SIL 2 Safety Instrumented Systems. The TP-700 sensor is SIL2 certified as an individual component, but it can be used
as part of a larger Safety Instrumented Systems as long as it is applied per the guidelines of this Safety Manual.

The TP-700 is SIL2 certified per IEC 61508-2010 with an HFT=0.

The revision levels of this SIL 2 certified TP-700 sensor is noted as Main PCB Rev 1, Amplifier PCB Rev 5, and
Firmware V5.14N.

7

SAFETY – CERTIFIED PRODUCT IDENTIFICATION

The model number printed on the label will include the character “S” in the model number string, indicating exida®
approval for SIL 2 standard. Example: Model TP-700 S.

8

CONSTRAINTS

The safety function of the Detcon Model TP-700 Hydrogen Sulfide Gas Sensor is limited by the following constraints:

- Shall not be used in continuous mode applications

- The maximum load on the 4-20mA output of the TP-700 is 1KΩ with 24VDC input power and 500Ω with

12VDC input power