Nature Power Inverter 2000W with 55Amp Inverter Charger (38326) User Manual

Page 12

background image

Page 12

>6Aac and <11Aac

15 Adc

>1Aac and <6Aac

35 Adc

<1Aac

55 Adc

Cb2

Same as above. Set the maximum current draw from shore power is 20A

>16Aac

5 Adc

>11Aac and <16Aac

15 Adc

>6Aac and <11Aac

35 Adc

<6Aac

55 Adc

Cb3

Same as above. Set the maximum current draw from shore power is 30A

>26Aac

5 Adc

>21Aac and <26Aac

15 Adc

>16Aac and <21Aac

35 Adc

<16Aac

55 Adc

Manufacturing Default Setting

Fd

Reset all settings to manufacturing default settings

(55A for 32326, In1, AL1, SdL, Flo, Cb3)

Understanding the Charger De-rating Current:

The charger current will be de-rated when the environment temperature reaches 60

°C (140 °F) or the internal temperature reaches the pre-set values.

Unit

De-rated Values

Internal Temperature

>90°C (194°F) Maximum charger will de-rated

to half

>95°C (203°F)

Charger current reduced to 5A

<85°C (185°F)

Charger current recover back

to set value

Environment Temperature

>60°C (140°F)

Charger current reduced to 5A

>55°C (131°F)

Charger current recover back

to set value

Enter Function Menu for unit setting:

To enter unit Function Menu, press and hold “Power” and “Select” button together for about 5

seconds until a beep is sounded.

When you are in Function Menu:

Press ‘Power’ button for 1 second to toggle between different Functions Menu like ‘Cu’, ‘In’,

‘AL’, ‘Sd’, ‘bAt’, ‘Cb’ and ‘Fd’ etc.

Press ‘Select’ button for 1 second to enter Individual Function Set Menu and you can

make change to the settings.

The unit will EXIT the Main Menu automatically if ‘Power’ and ‘Select’ buttons is not trigger

for more than 5 seconds.

When you are in Individual Function Set Menu:

Press ‘Select’ button for 1 second to toggle between different setting values.

Press ‘Select’ button for 5 seconds to set selected setting and exit to next Main Menu

See more details on flow chart below.