STARTUP & SAFE OPERATION

' Do not use a damaged unit. Check for shipping damage and place a claim with carrier if damage

is discovered.

' Return the Warranty Card to activate technical support service and warranty coverage.
' The AC2860 should not be operated or serviced by any person who has not read all the

contents of this manual.

' This manual describes normal operation and maintenance for the AC2860. Failure to read and

comply with these instructions or any one of the limitations noted herein can result in serious
injury and/or property damage. The instructions should not be interpreted to anticipate every
possible contingency.

' It is the responsibility of the owner/user to operate the AC2860 in accordance with all laws and

specifications which may apply.

' Recover (recycle) and charge only the refrigerants for which the AC2860 is configured.
' Avoid breathing refrigerant or lubricant vapor. Exposure may irritate eyes, nose and throat.

Ventilate work area if accidental system discharge occurs.

' Wear safety glasses and protective gloves. Refrigerant has a very low boiling point and can

cause frostbite.

' Follow the AC2860 operating procedures sequentially to avoid prematurely disconnecting hoses

or opening valves which may release refrigerant to the atmosphere.

' Do not expose the AC2860 to moisture or operate in wet areas.
' Use the AC2860 in locations with ventilation that provides at least four air changes per hour.
' Hoses must have shutoff devices within 12 inches of the connection point to the A/C to minimize

the introduction of air into the AC2860 and the release of refrigerant when being disconnected.

' Avoid using an extension cord with the AC2860. If necessary use a good condition, three wire

grounded, #14 AWG or larger extension cord of the shortest possible length.

' Disconnect power before performing any maintenance or service on the AC2860.
' Do not connect the red or blue hoses to the liquid port of a cylinder of refrigerant to fill the

charge cylinder. Doing so may cause the compressor to fail and void the warranty.

' Do not connect the AC2860 to the liquid side of any A/C with a capacity greater than 4 lbs.

Refrigerant in A/C Systems having larger capacities must be recovered from the vapor side only.

Special Considerations with R134a

R134a has been shown to be nonflammable at ambient temperature and atmospheric pressure.
However, tests under controlled conditions have indicated that at pressures above atmospheric and
with air concentrations greater than 60 percent by volume, R134a can form combustible mixtures.

While it is recognized that an ignition source is also required for combustion to occur, the presence
of combustible mixtures is a potentially dangerous situation and should be avoided.

Under no circumstances should any equipment be pressure tested or leak tested with air and
R134a mixtures. Do not use compressed air for leak detection in R134a systems.