MAHLE RTI TX200-UNDP User Manual
Page 6
Page 5
Connect TX200 Power Cord to a properly protected, grounded receptacle. Avoid using an extension cord. If
necessary, use a good condition, 3-wire grounded, 2.5 mm
2
extension cord of the shortest possible length.
The TX200 is now ready to recover refrigerant.
Press the top of the ON/OFF Switch. The switch will illuminate to indicate that power is on.
The COMPRESSOR ON Light will illuminate and the TX200 will begin recovering refrigerant.
The CYLINDER FULL Light will illuminate if the ERC Cylinder fills to capacity.
The TX200 will recover refrigerant until a vacuum is sensed. The Compressor will turn off and the Compressor-
On Light will turn off.
!
!
!
!
DO NOT TURN THE TX200 OFF OR DISCONNECT HOSES
!
!
!
!
A small quantity of Liquid refrigerant will probably remain in the A/C System. This liquid will vaporize (boil
up) and increase pressure in the system as components again warm to ambient temperature.
If pressure increases to a preset level, the TX200 will again start to recover refrigerant. The Compressor will
turn on and the Compressor-On Light will illuminate.
Figure 2 TX200 Control Panel