Contract or, Countinuous on – Thermolec Split|Steam User Manual
Page 31

CONTRACT
OR
Page 29
Number of
fl
ashes
of
the
red light
Error Description
Humidi
fi er
Status
Actions
to
be
T
aken
by the T
echnician
Reset
OFF
No error
The humidi
fi
er is working
fi ne
None
Countinuous
ON
The
fl
ood sensor under the tank
senses water in the pan.
Humidi
fi
er immediately suspends the
ongoing operation. Heating elements
and supply valve are switched of
f.
T
urn the main power OFF
, then
- Check the drain tube
- Check for abnormal leaks
Automatic Reset when
switching main power
ON
1
The two water level sensors are
miswired or do not read the water
level properly
.
Humidi
fi
er attempts to operate, then
stops because of wrong information
from water level sensors.
T
urn the main power OFF
, then
- Check that the water level
sensors are in the right order
-
Clean
the
sensors
Automatic Reset when
switching main power
ON
2
This code is not used on this
model - Reserved for future use
3
Inadequate water supply
.
The
supply valve was open for more
than 4 minutes.
Humidi
fi
er immediately suspends the
ongoing operation. Heating elements
and supply valve are switched of
f.
T
urn the main power OFF
, then
check the water supply circuit
Automatic Reset when
switching main power
ON
4
Inadequate drainage.
The tank
did not drain or the draining cycle
is too long.
Humidi
fi
er immediately suspends the
ongoing operation. Heating elements
and supply valve are switched of
f.
T
urn the main power OFF
, then
check the drain tube
Automatic Reset when
switching main power
ON
5
The fan is not running.
Humidi
fi
er immediately suspends
the ongoing operation.
The unit goes
back to normal operation as soon as
the error condition disappears.
Check the wiring between the fan
module and steam generator
.
Automatic Reset
when error conditions
disappear
6
T
emperature inside the tank
exceeded the high temperature
cut-out setting.
The high temperature cut-out has
tripped. The
humidi
fi er
immediately
suspends the ongoing operation.
Heating elements and supply valve
are switched of
f.
T
urn the main power OFF
, then
- Check the steam hose for kinks
or blockage
-
This is a very serious condition
After pushing on the
thermal cut-out button,
automatic reset when
switching main power
ON
22.