SPECIFICATIONS:

SENSOR

CALIBRATION

Type:

Catalytically

aided

platinum

bead Adjustments:

Zero,

span

Range: 0

100

LEL Test

Points:

Current,

voltage,

output

Response:

90% in 45 seconds

Typical Life: Three years in normal service

ENVIRONMENTAL (TEMPERATURE)

Zero Drift:

Less than 5% per year

Operating: -40° to 185° F (-40° to 85° C)

Humidity: 0- 99% RH, non condensing

ELECTRICAL DATA

CONSTRUCTION

Wiring:

3

wire

non-insolated

Electrical Class: Class 1, Div., Groups B, C & D

Input

Voltage:

11

30

VDC

Mounting:

Conduit

or

flexible

cable

Input

Current:

200

mA

at

24

VDC

Physical: 7.25”

x

3.5”

x

3.5”

Input

Power: 2.3

W (18.4

cm

x

8.9

cm

x

8.9

cm)

Output:

4

to

20mA

signal

Weight:

1.5

pounds

(0.68

kg)

Loop

Resistance:

800

Ohms

Housing: Cast

Aluminum


Partial List of Available Combustible Gases


Acetic Acid
Acetone
Acetylene
Butane
Iso-Butane
Butene-1
iso-Butyle Alcohol
ios-Butyl Benzene
Dimethylpentane
Ethane

Ethyl Acetate
Ethyl Alcohol
Ethylene
Diethyl Ether
Dimethyl Ether
Heptane
Hexane
Hydrogen
Methane
Methyl Acetate

Methyl Alcohol
Methylethyl Ketone
Natural Gas
Octane
Pentane
Propane
Propyl Alcohol
Toluene
Xylene
JP-4 (Jet Fuel)