HTP SuperStor Ultra Indirect Fired Water Heaters User Manual
Page 34
34
LP-83 Rev. 3.24.14
TROUBLESHOOTING
NO HOT WATER
PROBLEM
POSSIBLE SOLUTION
Zone valve not opening
Open manually to replace.
Circulator not operating
Check or replace
Tank control set too low
Raise tank temperature* (SEE NOTE BELOW)
Boiler control set too low
Raise boiler temperature
Wiring incorrect
Recheck wiring
Tank control failure
Replace control
Zone valve failure
Replace valve
Circulator failure
Replace circulator
Air trap in loop
Purge air
NOT ENOUGH HOT WATER
PROBLEM
POSSIBLE SOLUTION
Zone valve restriction
1” full bore replace zone valve
Circulator arrow reversed
Reverse circulator
Tank temperature too low
Raise tank temperature* (SEE NOTE BELOW)
Boiler temperature too low
Raise boiler temperature
Boiler sized too small
Check sizing chart
Tank sized too small
Check sizing chart
Demand flow rate too high
Install mixing valve, raise tank temperature*
Air trap in loop
Purge to remove air
Install flow regulator
Heat and tank come on together
Recheck wiring or set indirect as priority over central heating.
Draw tank down and lower thermostat. Recheck.
Not enough space heat
Boiler sized too small. Consult chart.
Slow recovery
Circulator head capacity too low
T & P VALVE DISCHARGES
PROBLEM
POSSIBLE SOLUTION
Tank temperature too high
Lower temperature on tank
Water expands when heated
Install expansion tank
Water pressure too high
Install pressure reducing valve
HOT TUBS, SPAS, MULTIPLE SHOWERS, HIGH DEMAND
PROBLEM
POSSIBLE SOLUTION
Pressure too low
Check line pressure for restriction
Recovery of tank slow
Slow startup boiler. See chart.
Not enough hot water
Boiler sized too small. See chart.
Check flow rate and compare to chart
Demand too great. Check flow rates and compare to chart. Install
mixing valve and/or flow restricting valve and raise tank and boiler
temperature*.
Table 10 - *See scald warning below.
When raising tank temperature, the risk of scald injury increases. To avoid scald injury, use a water tempering or mixing valve and
extreme caution when using hot water. Consult codes for conformance.