beautypg.com

Part 8, Gas piping, A. gas connection – HTP 399M User Manual

Page 51: B. gas piping, Part 8 – gas piping

background image

51

PART 8 – GAS PIPING

Failure to follow all precautions in this section could result in fire, explosion, severe injury or death!

A. GAS CONNECTION

Connect the gas supply to the system following state and local plumbing codes.

The gas supply shall have a maximum inlet pressure of less than 14" water column (350 mm), ½ pound pressure (3.5 kPa), and a
minimum of 3.5" water column. The entire piping system, gas meter and regulator must be sized properly to prevent pressure drop
greater than 0.5" WC as stated in the National Fuel Gas Code. This information is listed on the rating plate.

NOTE:

Maximum inlet gas pressure must not exceed 14” w.c. (3.5 kPa).


*NOTE: Installer must supply trap to meet local code requirements.

It is very important that you are connected to the type of gas noted on the rating

plate. “LP” for liquefied petroleum, propane gas, or

“NAT” for natural or city gas. Prior to turning the gas on, all gas connections must be approved by the local gas supplier or utility, in
addition to the governing authority.

The nipple provided is ½” with a factory installed ¾” bell reducer. DO NOT REMOVE this ¾” by ½” bell reducer! It is mandatory that this
fitting is used for connection to a field fabricated drip leg per the National Fuel Gas Code. Ensure that the entire gas line to the
connection i

s no smaller than ¾”.

Do not attempt to support the weight of gas piping with the boiler or its accessories. The gas valve and blower will not support the
weight of the piping. Failure to follow this warning could result in substantial property damage, severe personal injury, or death.

Once all inspections have been performed, the piping must be leak tested. If the leak test requirement is a higher test pressure than the
maximum gas inlet pressure, you must isolate the boiler from the gas line to continue leak testing. To do this, turn off the factory and
field-installed gas cocks. This will minimize the possibility of damaging the gas valve. Failure to do so may damage the gas valve. In the
event the gas valve is exposed to a pressure greater than ½ PSI, 14" water column, the gas valve must be replaced. Never use an
open flame (match, lighter, etc.) to check gas connections.

Refer to the table below to size the supply piping to minimize pressure drop between meter or regulator and unit.

Maximum capacity of pipe in cubic feet of gas per hour for gas pressures of .5 psi or less and a pressure drop of .3 inch water column:

Nominal Iron

Pipe Size

(Inches)

Internal

Diameter

(Inches)

Length of Pipe (Feet)

BTU’s

Per Hour

x

1,000

10

20

30

40

50

60

70

80

90

100

125

150

175

200

¾

.824

278

190

152

130

115

105

96

90

84

79

72

64

59

55

1

1.049

520

350

285

245

215

195

180

170

160

150

130

120

110

100

1 ¼

1.380

1,050

730

590

500

440

400

370

350

320

305

275

250

225

210

1 ½

1.610

1,600

1,100

890

760

670

610

560

530

490

460

410

380

350

320

Table 9

It is recommended that a soapy solution be used to detect leaks. Bubbles will appear on the pipe to indicate a leak is present. The gas
piping must be sized for proper flow and length of pipe to avoid excessive pressure drop. Both the gas meter and the gas regulator
must be properly sized for the total gas load. If you experience a pressure drop greater than 1" WC, the meter, regulator or gas line is
undersized or in need of service. You can attach a manometer to the incoming gas drip leg by removing the cap. The gas pressure
must remain between 3.5" WC and 14" WC during stand-by (static) mode and while in operating (dynamic) mode at full output.

If an in-line regulator is used, it must be a minimum of 10 feet from the boiler. It is very important that the gas line is properly
purged by the gas supplier or utility. Failure to properly purge the lines or improper line sizing will result in ignition failure.

This problem is especially noticeable in NEW LP installations and also in empty tank situations. This can also occur when a utility
company shuts off service to an area to provide maintenance to their lines. The gas valve must not be replaced with a conventional gas
valve under any circumstances. As an additional safety feature, the gas valve in this boiler has a flanged connection to the swirl plate
and blower.

B. GAS PIPING

1. Run the gas supply line in accordance with all applicable codes.

This manual is related to the following products: