7. Start capacitor open or shorted

blown.

8. Run capacitor open, shorted or

blown.

9. Relay defective or burned out.

10. Product zone temperature too

high.

11. Suction line frosted or sweating.

12. Liquid line frosted or sweating.

13. Noisy condensing unit.

1. Relay contacts not opening

properly.

2. Prolonged operation on start cycle

due to:

a. Low voltage to unit.

b. Improper relay.

c. Starting load too high.

3. Excessive short cycling.

4. Improper capacitor.

1. Improper capacitor.

2. Excessively high line voltage

(110% of rated-max.)

1. Incorrect relay.

2. Incorrect mounting angle.

3. Line voltage too high or too low.

4. Excessive short cycling.

5. Relay being influenced by loose

vibrating mounting.

6. Incorrect run capacitor.

1. Control setting too high.

2. Inadequate air circulation.

1. Overcharge of refrigerant.

2. Evaporator fan not running.

3. If remote model, expansion valve

stuck open.

4. If remote model expansion valve

is passing excess refrigerant or is

oversized.

1. Restriction in dehydrator or

strainer.

2. Liquid shut-off (king valve)

partially closed.

1. Loose parts or mounting.
2. Tubing rattle.

3. Bent fan blade causing vibration.

4. Fan motor bearings worn.

1. Clean contacts or replace relay if

necessary.

2.

a. Determine reason and correct.

b. Replace.

c. Correct by using pump down

arrangement if necessary.

3. Determine reason for short cycling

(see 5 above) and correct.

4. Determine correct size and

replace.

1. Determine correct size and

replace.

2. Determine reason and correct.

1. Check and replace.

2. Remount relay in correct position.

3. Determine reason and correct.

4. Determine reason (see 5 above)

and correct.

5. Remount rigidly.

6. Replace with proper capacitor.

1. Reset control.

2. Rearrange product load to

improve air circulation.

1. Correct charge.

2. Determine reason and correct.

3. Clean valve of foreign particles.

Replace if necessary.

4. Readjust valve or replace with

smaller valve.

1. Replace part.

2. Open valve fully.

1. Find and tighten.
2. Reform to be free of contact.

3. Replace blade.

4. Replace motor.

PROBLEM

POSSIBLE CAUSE

REMEDY

TROUBLESHOOTING & SERVICING REFRIGERATION SYSTEM