MaxPower Corp Eternalite3 User Manual
Page 2

Represented by:
Email: [email protected]
1921 S. Quaker Ridge Place
Ontario, CA 91761
Ph: 1.877.DSPM POWER
1.877.377.6769
Fax: (909)930-3335
*Standard Power Levels..........**3.0, 4.5, 6.0, 8.0, 10.0, 12.0, 16.0, 20.0,
24.0, 30.0, 40.0, 60.0, 80.0, 100.0 and 125.0 KW
*Input Voltage ..........................208Y/120, 480Y/277, 208 or 480VAC
*Input Voltage Range...............+10%. -15%
*Output Voltage........................208Y/120 or 480Y/277 VAC
*Output Voltage Regulation......±3% for all loads and battery discharge mode
*Output Frequency Range........60 Hz, ±1%
Output Wave Form...................Sine-wave <5% @ 100% linear load
Crest Factor..............................2.5:1 typical
Input Protection........................Input Main Circuit Breaker
Output Protection.....................Output Main Circuit Breaker
Surge Protection......................The unit will protect itself and the load
against surges as defined in
ANSI/EEE C62.45 category A and B
Battery......................................Sealed maintenance-free (AGM) lead calcium
Recharge Current.....................Conforms to UL924 standards
External Battery........................Provision for hardware connection of
external battery cabinets or DC source
Efficiency..................................≥92% at 100% linear load
Audible Noise...........................<45dB measured on Response Curve “A”
Safety Agencies.......................Listed to UL standard 924
Operating Temperature............0º to 40ºC (32º to 104ºF)
Storage Temperature...............-20º to 60ºC (-4º to 140ºF)
Humidity...................................5 - 95%, Non-condensing
*Consult factory for others.
**No line to line loads for 3.0 - 6.0 kw units.
Specifications subject to change without notice.
Options:
ECM - Environmental Control Module
NOF120 - Normally OFF Circuit 120VAC
NOF227 - Normally OFF Circuit 277VAC
NOH120 - Normally OFF “Hold On” 120VAC
NOH227 - Normally OFF “Hold On” 277VAC
OCB - Output Circuit Breaker(s)
EPO- Emergency Power Off
RSSP - Remote Indicator Panel
EIR - Ethernet Interface with RS232
FAX - Fax Modem
FC - Form C Contacts
SRB - Seismic-Rated Bracket
STU3 - Onsite Startup
IDB - Internal Dimmer Bypass
EMB - External Maintenance Bypass
EW - Extended Warranty
UPS
Battery
Weight
Power
Rating
Eternalight
3
Series
OE3
(Consult
factory
for others)
Cabinet
Dimensions
Cabinet
Dimensions
(combined)
KVA/KW
W
H
D
W
No.
H
D
3
42”
71”
22.5”
not required
4.5
42”
71”
22.5”
not required
6
42”
71”
22.5”
not required
8
42”
71”
22.5”
42”
1
71”
22.5”
10
42”
71”
22.5”
42”
1
71”
22.5”
12
42”
71”
22.5”
42”
1
71”
22.5”
16
42”
71”
22.5”
42”
1
71”
22.5”
20
42”
71”
22.5”
42”
2
71”
22.5”
24
42”
71”
22.5”
42”
2
71”
22.5”
30
42”
71”
22.5”
42”
2
71”
22.5”
40
42”
71”
22.5”
42”
3
71”
22.5”
60
50”
71”
32”
80
50”
71”
32”
100
50”
71”
32”
125
50”
71”
32”
980
1100
1350
1700
2250
2700
2950
3800
4350
5150
6790
Consult Factory
Consult Factory
Consult Factory
Consult Factory
(lbs)