beautypg.com

Applications, Technical specifi cations – MaxPower Corp FirstLine 924 20, 30kW User Manual

Page 2

background image

Applications

Public Buildings

Commercial and

Industrial

Facilities

Infrastructure Systems

High Security Areas

Schools, Universities

Single Point of Power

Protection

In the event of an AC power failure, FirstLine

®

924

automatically supports the connected lighting loads on
battery power and will continue to provide power without
any interruption for a full 90 minutes. When the utility power
returns to normal, FirstLine

®

924 will automatically recharge

the batteries to be ready for the next power disturbance.

Technical Specifi cations

Three-Phase Central Inverter for
Emergency Lighting Applications

General

On-line double-conversion topology

True sine wave output

Continuous, no-break operation

Three-phase system will support single

or three-phase loads

LCD front panel monitoring and control

Automatic system bypass

Circuit breaker protection integral with

battery cabinet, molded-case type

Input

Input Voltage Rating: 208Y/120 and

480Y/277 standard, Delta connection

with optional isolation transformer

Input Voltage Range:

+

/

-

10% system

start-up;

+10% /-20% from nominal

Input frequency: 60Hz

+

/

-

5%

Full load walk-in from 25% to 100% of

rated load in <5 seconds

Harmonic current distortion <5% at full load

Surge Withstand: Meets IEEE C62.41

Output

IGBT: true sine wave PWM inverter

Inverter output distortion: <5% THD

(100%

non-linear)

Inverter output distortion: <2% THD

(linear

loads)

Voltage regulation:

+

/

-

1% of nominal

at full load

Frequency: 60 Hz

Battery

Designed for easy maintenance

Standard backup time of 90 minutes at

full

load

Valve-Regulated Lead-Acid (VRLA) battery

10 year design life at 77°F (25°C)

Housing

Freestanding, NEMA 1 steel enclosure

Service access—top, front, all (4) sides

Bottom access for conduit entries

Environmental

Agency Compliance: UL924, FCC and

CSPR22, Class A

Operating temperature range 18°F (-8°C)

to 104°F (40°C)

Acoustical Noise: 75 db at 3 feet

Relative Humidity: 0-95% non-condensing

Meets NFPA 101 Life Safety, and

NEC

codes

Seismic Zone 4 certifi ed

Monitoring/Communications

Front Panel LCD Display

4 x 16 character display

System status and alarms

Communications Port

RS-232

Dry Contact (AS/400)

Remote monitoring

SNMP available option

In addition to meeting

life safety requirements,

the FirstLine

®

924 can

also increase the life

expectancy of the

protected lighting system

and reduce long-term

cost of ownership.

Your tailored power solutions provider