Applications, Technical specifi cations – MaxPower Corp FirstLine 924 8, 12, 16kW User Manual
Page 2

Applications
■
Public Buildings
■
Theaters
■
Schools
■
Parking Garages
■
Housing Complexes
In the event of an AC power failure, FirstLine
®
924
automatically supports the connected lighting loads on
battery power and will continue to provide power without
any interruption for a full 90 minutes. When the utility power
returns to normal, FirstLine
®
924 will automatically recharge
the batteries to be ready for the next power disturbance.
Technical Specifi cations
Three-Phase Central Inverter for
Emergency Lighting Applications
General
■
On-line double-conversion topology
■
True sine wave output
■
Continuous, no-break operation
■
Three-phase system will support single
or three-phase loads
■
LCD front panel monitoring and control
■
Automatic system bypass
Input
■
Input Voltage Rating: 208Y/120 and
480Y/277 standard, Delta optional
with
transformer
■
Input Voltage Range: +/-10% system
start-up;
+10% /-15% operation
(166-250Vac,
384-576Vac)
■
Input frequency: 60Hz +/-5%
■
Full load walk-in from 25% to 100% of
rated load in <5 seconds
■
Surge Withstand: Meets IEEE C62.41
Output
■
IGBT: true sine wave PWM inverter
■
Inverter output distortion: <5% THD
(100%
non-linear)
■
Inverter output distortion: <2% THD
(linear
loads)
■
Voltage regulation: +/-1% of nominal
at full load
■
Frequency: 60 Hz
Battery
■
Designed for easy maintenance
■
Standard backup time of 90 minutes at
full
load
■
Valve-Regulated Lead-Acid (VRLA) battery
■
10 year design life at 77°F (25°C)
■
Quick recharging times
Housing
■
Freestanding, NEMA 1 steel enclosure
■
Front and top service access
■
Bottom access for conduit entries
■
Various battery cabinet confi gurations
Environmental
■
Agency Compliance: UL924, FCC and
CSPR22, Class A
■
Operating temperature range 18°F (-8°C)
to 104°F (40°C)
■
Acoustical Noise: 65 db at 3 feet
■
Relative Humidity: 0-95% non-condensing
■
Meets NFPA 101 Life Safety, and
NEC
codes
■
Seismic Zone 4 certifi ed
Monitoring/Communications
■
Front Panel LCD Display
●
4 x 16 character display
●
System status and alarms
■
Communications Port
●
RS-232
●
Dry Contact (AS/400)
●
Remote monitoring
●
SNMP available option
In addition to meeting
life safety requirements,
the FirstLine
®
924 can
also increase the life
expectancy of the
protected lighting system
and reduce long-term
cost of ownership.
Your tailored power solutions provider