Technical specifications – GeneralAire EDMK4 Elite Steam User Manual
Page 24

Elite Steam +030222075 Rev. 3.5 – July 2012
24
8. TECHNICAL SPECIFICATIONS
Steam flows, VAC, kW
5.5 lbs/hr (2.5 kg/h): 110 VAC 1-phase 50-60 Hz, 1.86 kW
12 lbs/hr (5.4 kg/h): 230 VAC 1-phase 50-60 Hz, 4.05 kW
Notes
Steam pressure
3.81 in WC / 950 Pa
For duct only
Dimensions (mm )
24” x 14” x 8” (600 x 341 x 204 mm)
(Height x Width x Depth)
Weight empty/packaged/installed
with water
18/22/26 lbs. (8/10/12 kg)
IP class
IP20
Electrode power cables
12 AWG
Power relays
2 x 30 Amp
on board
Ground connection
Screw
Input water type
Potable water
no demin. or softened water
Conductivity range
125-1250 µS/cm
Special cylinders for cond. < 350
Water fill connection
1/4” O.D. Compression
Adapter to ¾” FPS
Water fill - instant flow
0.09 – 0.16 gpm
(0.35 – 0.60 l/min)
Drain connection
32 mm O.D. (1.25”)
Adjustable from horizontal to
vertical.
May be from back or bottom of
unit.
Drain water temp
< 140°F
(< 60°C)
drain tempering device
Drain flow
Initial Max drain rate - 7 gpm (26.2 l/min) (w/ full cylinder –
for the first 10-15 seconds of drain cycle)
Average drain rate – 3.1 gpm (11.7 l/min) (measured over a
one minute period starting with full cylinder)
Embedded fan flow
71 cfm
(120 m³/hr)
Direct Room Discharge Only
Serial communication
RS485