151 - 302 V

Batteries & Runtime

Battery type

Maintenance-free sealed Lead-Acid battery
with suspended electrolyte : leakproof

Replacement battery cartridge

RBC43

RBC™ Quantity

1

Typical backup time
at half load

15.7 minutes (990 Watts)

Typical backup time
at full load

5.2 minutes (1980 Watts)

Runtime Chart

Smart-UPS

Communications & Management

Interface port

DB-9 RS-232, SmartSlot, USB

Available Smart Slot Interface Quantity

1

Control panel

LED status display with load and battery bar-
graphs and On Line : On Battery : Replace
Battery : and Overload Indicators

Audible alarm

Alarm when on battery : distinctive low
battery alarm : configurable delays

Emergency Power Off (EPO)

Yes

Surge Protection and Filtering

Surge energy rating

480 Joules

Filtering

Full time multi-pole noise filtering : 0.3%
IEEE surge let-through : zero clamping
response time : meets UL 1449

Physical

Maximum height

4 inches ( 8.89 cm )

Maximum width

19 inches ( 48.26 cm )

Maximum depth

26 inches ( 66.04 cm )

Rack Height

2 U

Net weight

96 lbs. ( 43.64 kg )

Shipping Weight

125 lbs. ( 56.82 kg )

Shipping Height

10 inches ( 25.40 cm )

Shipping Width

25 inches ( 62.23 cm )

Shipping Depth

39 inches ( 98.04 cm )

Color

Black

Units per Pallet

8

Environmental

Operating Environment

0 - 40 °C ( 32 - 104 °F )

Operating Relative Humidity

0 - 95 %

Operating Elevation

0-10000 feet ( 0-3000 meters )

Storage Temperature

-15 - 45 °C ( 5 - 113 °F )

Storage Relative Humidity

0 - 95 %

Storage Elevation

0-50000 feet ( 0-15000 meters )

Online thermal dissipation

300 BTU/hr

more details...

Topology:

Line Interactive

Page 2 of 3

APC Smart-UPS 2200VA USB & Serial RM 2U 230V

9/3/2548

http://www.apcc.com/resource/include/techspec_index.cfm?base_sku=SUA2200RMI2U

This manual is related to the following products: