beautypg.com

A.O. Smith NW 37-670 User Manual

Page 7

background image

7

Calculating Amperage/Overcurrent Protection

The boiler is factory wired for connection to three wire single-phase
or three and four wire three-phase branch circuits. In addition, a
ground conductor may be required.

A diagram of the wiring is furnished with the boiler for the electrician’s
use. An amperage table is on page 4 of this manual. The boiler
model and rating plate provides full load amperage data.

The rating of the overcurrent protection should be computed on the
basis of 125 percent of the total connected load amperage. Where
the standard ratings and settings do not correspond with this
computation, the next higher standard rating or setting should be
selected.

Boiler Circuits

The boiler’s electrical components are pictured and identified on page
5. The model and rating plate illustration on page 4 identifies the
electrical characteristics. Basically, there are two electrical circuits:

The control circuit, where the temperature control directly or
indirectly operates the contactor coils.

The power circuit, which is operated by the control circuit, carries
the electrical load of the heating elements.

The following describes the circuits and includes typical wiring
diagrams. All circuits are designed for 60 or 50 Hertz alternating
current.

Refer to ELECTRICAL CONFIGURATION TABLE, below, and wiring
diagram provided with your boiler before completing connections to
electrical supply.

NOTE: Wiring diagrams in this manual are typical examples. The
specific wiring diagram for your boiler is the one supplied with the
boiler.

Control Circuit

All control circuits are operated on single-phase 120V. A transformer
is used in the control circuit.

Control circuit wiring is 14 Awg, THHN or THWN type, rated 600 volts,
105°C.

Seperate instructional literature is provided with the boiler for the
modulating solid state step control.

Portion of Table 310-16

Allowable Ampacities of Insulated

Copper Conductors

Not more than three conductors in

raceway or cable or direct burial

(based on ambient temperature of

30°C, 86°F.)

Portion of Table 310-16

Allowable Ampacities of

Insulated Aluminum and Copper-

Clad AluminumConductors

Not more than three conductors

in raceway or cable or direct

burial (based on ambient

temperature of 30°C, 86°F.)

Temperature Rating of

Temperature Rating of

Conductor. See Table Conductor. See Table

Size

310-13 in Code

Size

310-13 in Code

AWG

75°c

AWG

75°C

MCM

(167°F)

MCM

(167°F)

TYPES

TYPES

RH, RHW, RUH

RH, RHW, RUH

(14-2),

(12-2),

THW, THWN,

THW, THWN,

XHHW, USE

XHHW, USE

18

- - - - -

12

15

16

- - - - -

10

25

14

15

8

40

12

20

6

50

10

30

4

65

8

45

3

75

6

65

2

90

4

85

1

100

3

100

1/0

120

2

115

2/0

135

1

130

3/0

155

1/0

150

4/0

180

2/0

175

250

205

3/0

200

300

230

4/0

230

350

250

250

255

400

270

300

285

500

310

350

310

600

340

400

335

700

375

500

380

750

385

600

420

800

395

700

460

900

425

750

475

1000

445

800

490

1250

485

900

520

1500

520

1000

545

1750

545

1250

590

2000

560

1500

625

1750

650

2000

665

These capacities relate only to conductors
described in Table 310-13 in Code.

For ambient temperatures over 30°C, see

Correction Factors, Note 13 in Code

Power Circuit

The boiler is equipped with one of the power circuit configurations
shown in the table.

Power circuit wiring is type THHN, rated 600 volts, 105°C, sized as
necessary.