Gorman-Rupp Pumps PA6C60-4045H 1485126 and up User Manual
Page 13
OM−06081
PA SERIES
PAGE B − 6
INSTALLATION
Float Switch Installation
The Float Switch autostart system employs either a
single or double float switch, where a bulb raises or
lowers (floats) with the liquid level, thus activating
an enclosed miniature switch. The floats are
equipped with a socket type connector that plugs
into a matching receptacle on the auto-start control
box.
Standard floats are equipped with 50 feet (15,2 m)
of cable.
When installing the floats, note the following:
a. Be sure to provide sufficient room in the wet
well or sump so that floats do not get ob-
structed or drawn into the suction line. If a flex-
ible suction hose is used, it may be extended
to lay along the bottom of the wet well or sump
and the float can be attached to the hose
above the point where it bends along the bot-
tom. Direct the suction line toward the flow,
and the float(s) away from the flow. If a stand-
pipe is available, attach the float switch cable
to the standpipe in the sump at the approxi-
mate desired liquid level.
b. In a single float system, the cable can be teth-
ered to the suction line or standpipe approxi-
mately 6 inches (152 mm) above the float.
This setting allows approximately 9 inches
(229 mm) of liquid rise between pump start/
stop. The start/stop interval may be increased
by extending the float end of the cable. The
liquid level in the sump will increase approxi-
mately 8 inches (203 mm) between start/stop
intervals for every 6 inches (152 mm) of cable
increase.
c. If a double float switch system is used, posi-
tion the Start" float at the desired high water
level in the sump, and the Stop" float at the
desired low water level in the pump.
d. Refer to Figure 3 for additional float switch
data.
OPERATING
RANGE
(See Table Below)
CABLE
TETHER
POINT
OFF
(Emptying)
ON
(Filling)
ON
(Emptying)
OFF
(Filling)
1.25" Pipe
(Not Furnished)
ENGINE
CONTROL
BOX
1.0
(0.3)
APPROXIMATE FREE CORD LENGTH IN FT. (M)
0.5
(.15)
1.0
(0.3)
1.5
(.46)
2.0
(0.6)
2.5
(.76)
3.0
(0.9)
2.0
(0.6)
3.0
(0.9)
4.0
(1.2)
Figure 3. Float Switch Data