beautypg.com

Gorman-Rupp Pumps PAH3A60-6068H 1522805 and up User Manual

Page 14

background image

OM-06469

PAH SERIES

PAGE B - 6

INSTALLATION

Float Switch Installation

The Float Switch autostart system employs either a
single or double float switch, where a bulb raises or
lowers (floats) with the liquid level, thus activating
an enclosed miniature switch. The floats are
equipped with a socket type connector that plugs
into a matching receptacle on the auto‐start control
box.

Standard floats are equipped with 50 feet (15,2 m)
of cable.

When installing the floats, note the following:

a. Be sure to provide sufficient room in the wet

well or sump so that floats do not get ob­
structed or drawn into the suction line. If a flex­
ible suction hose is used, it may be extended
to lay along the bottom of the wet well or sump
and the float can be attached to the hose
above the point where it bends along the bot­
tom. Direct the suction line toward the flow,
and the float(s) away from the flow. If a stand­

pipe is available, attach the float switch cable
to the standpipe in the sump at the approxi­
mate desired liquid level.

b. In a single float system, the cable can be teth­

ered to the suction line or standpipe approxi­
mately 6 inches (152 mm) above the float.
This setting allows approximately 9 inches
(229 mm) of liquid rise between pump start/
stop. The start/stop interval may be increased
by extending the float end of the cable. The
liquid level in the sump will increase approxi­
mately 8 inches (203 mm) between start/stop
intervals for every 6 inches (152 mm) of cable
increase.

c. If a double float switch system is used, posi­

tion the “Start” float at the desired high water
level in the sump, and the “Stop” float at the
desired low water level in the pump.

d. Refer to Figure 3 for additional float switch

data.

OPERATING

RANGE

(See Table Below)

CABLE

TETHER

POINT

OFF

(Emptying)

ON

(Filling)

ON

(Emptying)

OFF

(Filling)

1.25” Pipe
(Not Furnished)

ENGINE

CONTROL

BOX

1.0

(0.3)

APPROXIMATE FREE CORD LENGTH IN FT. (M)

0.5

(.15)

1.0

(0.3)

1.5

(.46)

2.0

(0.6)

2.5

(.76)

3.0

(0.9)

2.0

(0.6)

3.0

(0.9)

4.0

(1.2)