Gorman-Rupp Pumps T10A61S-B /FM User Manual
Page 12
OM-05444
SUPER T SERIES
PAGE B - 5
INSTALLATION
Do Not install a manual shut‐off valve in a bypass
line. If a manual shut‐off valve is installed to facili
tate service of the Air Release Valve, the valve must
not be left closed during operation. See the sup
plement at the end of this section for additional in
formation on bypass lines and the Gorman‐Rupp
Automatic Air Release Valve.
NOTE
The bypass line may clog occasionally, particularly
when pumping liquids containing large solids. If
clogging occurs, locate and remove the clog. If the
clog is located between the discharge check valve
and the Air Release Valve, the valve will not close. If
the clog is located in the Relief Valve itself, or in the
line between the Relief Valve and the sump, the
valve will not open.
Do not terminate the discharge line at a level lower
than that of the liquid being pumped unless a si
phon breaker is used in the line; otherwise, a si
phoning action could result, causing damage to
the pump.
In low discharge head applications (less than 30
feet or 9,1 meters), it is recommended that the by
pass line be run back to the wet well, and located 6
inches (152,4 mm) below the water level or cut‐off
point of the low level pump. In some installations,
this bypass line may be terminated with a six‐to‐
eight foot length of 1‐1/4 inch (31,8 mm) I.D.
smooth‐bore hose; air and liquid vented during
the priming process will then agitate the hose and
break up any solids, grease, or other substances
likely to cause clogging.
A bypass line that is returned to a wet well
must be secured against being drawn into
the pump suction inlet.
It is also recommended that pipe unions be in
stalled at each 90
_ elbow in a bypass line to ease
disassembly and maintenance.
In high discharge head applications (more than
30 feet or 9,1 meters), an excessive amount of liq
uid may be bypassed and forced back to the wet
well under the full working pressure of the pump;
this will reduce overall pumping efficiency. There
fore, it is recommended that a Gorman‐Rupp
Automatic Air Release Valve be installed in the
bypass line.
Gorman‐Rupp Automatic Air Release Valves are
reliable, and require minimum maintenance. See
AUTOMATIC AIR RELEASE VALVE in this section
for installation and theory of operation of the Auto
matic Air Release Valve. Consult your Gorman‐
Rupp distributor, or contact the Gorman‐Rupp
Company for selection of an Automatic Air Release
Valve to fit your application.
A manual shut‐off valve should not be
installed in any bypass line. A manual
shut‐off valve may inadvertently be left
closed during operation. A pump which
has lost prime may continue to operate
without reaching prime, causing dan
gerous overheating and possible explo
sive rupture of the pump casing. Per
sonnel could be severely injured.
Allow an over‐heated pump to cool be
fore servicing. Do not remove plates,
covers, gauges, or fittings from an over‐
heated pump. Liquid within the pump
can reach boiling temperatures, and va
por pressure within the pump can cause
parts being disengaged to be ejected
with great force. After the pump cools,
drain the liquid from the pump by re
moving the casing drain plug. Use cau
tion when removing the plug to prevent
injury to personnel from hot liquid.
AUTOMATIC AIR RELEASE VALVE
When properly installed, a Gorman‐Rupp Auto
matic Air Release Valve will permit air to escape
through the bypass line and then close automati
cally when the pump is fully primed and pumping
at full capacity.