Automatic air release valve – Gorman-Rupp Pumps 88A52-B 1363098 and up User Manual
Page 12
80 SERIES
OM−00990
PAGE B − 5
INSTALLATION
If the application involves a high discharge
head, gradually close the discharge
throttling valve before stopping the pump.
Bypass Lines
If a system check valve is used due to high dis-
charge head, it may be necessary to vent trapped
air from the top of the pump during the priming
process. This may be accomplished by installing a
bypass line from the top of the pump, back to the
source of liquid. The end of the bypass line must be
submerged. The line must be large enough to pre-
vent clogging, but not so large as to affect pump
discharge capacity.
AUTOMATIC AIR RELEASE VALVE
When properly installed, a Gorman-Rupp Auto-
matic Air Release Valve will permit air to escape
through the bypass line and then close automati-
cally when the pump is fully primed and pumping
at full capacity.
Some leakage (1 to 5 gallons [3.8 to 19
liters] per minute) will occur when the
valve is fully closed. Be sure the bypass
line is directed back to the wet well or
tank to prevent hazardous spills.
Consult the manual accompanying the Air Release
Valve for additional information on valve installation
and performance.
Air Release Valve Installation
The Automatic Air Release Valve must be inde-
pendently mounted in a horizontal position and
connected to the discharge line of the self-priming
centrifugal pump (see Figure 3).
NOTE
If the Air Release Valve is to be installed on a staged
pump application, position the air release valve as
close as possible to the discharge check valve.
DISCHARGE PIPE
DISCHARGE
CHECK VALVE
PUMP DISCHARGE
SELF-PRIMING
CENTRIFUGAL
PUMP
SUCTION
LINE
SUPPORT
BRACKET
CLEAN-OUT
COVER
INSTALL AIR RELEASE VALVE
IN HORIZONTAL POSITION
90
_ LONG
RADIUS
ELBOW
WET WELL
OR SUMP
BLEED LINE 1"
(25,4 MM) DIA. MIN.
(CUSTOMER FUR-
NISHED) EXTEND 6"
(152 MM) BELOW
PUMP OFF LIQUID
LEVEL
Figure 3. Typical Automatic Air Release Valve Installation