INSTRUCTION MANUAL

• Before using this product read and understand instructions.
• Save these instructions for future reference.

• All work must be performed by qualified personnel trained in the proper

application, installation, and maintenance of plumbing, steam, and electrical

equipment and/or systems in accordance with all applicable codes and

ordinances.

• To prevent electrical shock, turn off the electrical power before making

electrical connections.

• The low water cut-off switch must be installed in series with all other limit

and operating controls installed on the boiler. After installation, check for

proper operation of all of the limit and operating controls, before leaving

the site.

• We recommend that secondary (redundant) Low Water Cut-Off controls be

installed on all steam boilers with heat input greater than 400,000

BTU/hour or operating above 15 psi steam pressure. At least two controls

should be connected in series with the burner control circuit to provide

safety redundancy protection should the boiler experience a low-water

condition. Moreover, at each annual outage, the low water cutoffs should

be dismantled, inspected, cleaned, and checked for proper calibration and

performance.

• To prevent serious personal injury from steam and hot water make sure

there is a discharge line from the blow down valve to a proper place of

disposal.

• To prevent a fire,do not use this low water cut-off to switch currents over

7.2A, 1/3 HP at 120 VAC or 3.6A, 1/3 HP at 240 VAC, unless a starter or

relay is used in conjunction with it.

!

WARNING

No. 11, 11M and 11MV

Replacement Switch

For use on Series 61, 64, 764, 67,

767, 69 and 70 Low Water Cut-Offs
11

General Purpose (BLACK terminal panel)

11M

Manual Reset Option (BLACK terminal panel)

11MV Millivolt / 24V Option (RED terminal panel)

Electrical Ratings

Motor Switch Rating

(Amperes)

Voltage Full Load Locked Rotor

Pilot Duty

120 VAC

120 VA at

240 VAC

120 or 240 VAC

NOTE: 11MV is rated at 24VA @ 24 VAC to 120 VAC

MM-705D

California Proposition 65 warning! This product contains chemicals known

to the state of California to cause cancer and birth defects or other
reproductive harm.

Previous controls should never be installed on a new system. Always

install new controls on a new boiler or system

Failure to follow this warning could cause property damage, personal

injury or death.

CAUTION:

A more frequent replacement interval may be necessary based on the con-

dition of the unit at time of inspection. McDonnell & Miller's warranty is one

(1) year from date of installation or two (2) years from the date of manufacture.