Flow rates, Installation, Step 1 - determine the location of the flow switch – Xylem MM 616F Series FS-5 General Purpose Liquid Flow Switch User Manual
Page 3
![background image](/manuals/311246/3/background.png)
FLOW RATES
Settings will vary when used to sense flow of other
fluids.
3
NOTE:
DO NOT USE LIQUID FLOW
SWITCHES ON SYSTEMS WITH
FLOW VELOCITY GREATER THAN
10 FEET (3M) PER SECOND.
INSTALLATION –
STEP 1 - Determine the Location of the Flow Switch
Fluid Flow
3/4
" or 1"
PIPE
5 x D
MINIMUM
D
D= PIPE DIAMETER
5 x D
MINIMUM
• The flow switch
should be located in a horizontal
section of pipe where there is a straight horizontal run
of at least 5 pipe diameters on each side of the flow
switch.
• The flow switch
must be installed in the upright
position as shown with arrow mark on side of casting
in the same direction as fluid will flow.
• Some system conditions that require more than 5 pipe
diameters are high viscosity fluid and high fluid velocity.
• The flow switch should be installed in the pump suction
piping when spring-loaded check valves and/or other
close coupled accessories are installed in the pump
discharge piping.
Flow Rates
Pipe
Mode of Operation
Size NPT
Flow
No Flow
in. (mm)
Settings
gpm (lpm)
gpm (lpm)
3
⁄
4
(20)
Factory or
or
Minimum
1.5
(5.7)
1.1
(4.2)
16.62 (63)
1
(25)
Maximum
15 (56.8)
10
(37.9)
27 (102)
Values are ± 10%
Max. Flow
Rate gpm
(lpm) w/o
Paddle Damage
NOTE: THIS PRODUCT IS NOT INTENDED
FOR USE IN POTABLE WATER
APPLICATIONS.
calculated using clean water in a horizontal pipe.
Flow rates required to activate the flow switch
are shown in chart below.These values were