c) Install the pressure readout fittings into the valve
body using the extension adapters first. Then install
the pressure and temperature access port onto the
extension adapter
1
/
4
inch NPT end.
OPERATING INSTRUCTIONS
Operation of the Wafer Valve is fully automatic and does not
require any adjustment. It automatically maintains the
selected flow over the designed differential pressure range.
HOW TO USE AUTOMATIC FLOW-LIMITING
VALVE PRESSURE TAPS TO DETERMINE
PROPER FUNCTIONING OF VALVE.
1.
Using Bell & Gossett Model RP-250 readout probes,
attach a Bell & Gossett differential pressure readout kit to
the readout valves on the Automatic Flow-Limiting Valve.
2.
Read the differential pressure across Wafer Valve. This
can be compared to system pump head to determine
valve function, and system flow blockage.
SERVICE INSTRUCTIONS
Should the Wafer Valve require cleaning or changing the
orifice, consult the following instructions.
1.
Remove the valve body from the piping system by
unbolting it from the two flanges on either side. Use the
lifting lug (eye-bolt for 4" thru 20") to handle/carry the
valve.
2.
Pull the cartridge assembly from the valve body for
cleaning or change to new flow cartridge. The cartridge is
secured to the mid-plate of the housing by means of 2 or
3 allen head screws. Remove the screws first. Then pull
the cartridge out of the mid-plate bore. Checking the
cartridge by pushing the orifice washer in to the cartridge
housing against the spring force for several times to
make sure spring is functional. Inspect the interior of
cartridge for broken spring or any particles stuck inside
that may prevent free movement of the cartridge housing.
3.
To change the orifice washer (for different flow rate),
remove the clip ring from inside the cartridge housing
with a screwdriver. Pull the orifice washer out and
replace it with the new orifice (orifice part number should
be facing upward). Push the new orifice in until it seats all
the way to the bottom of the shelf.
4.
Reinstall, or replace the clip ring in the cartridge-housing
groove and make sure that it is holding the new orifice
disk securely in place.
5.
Reassemble the cartridge into the mid-plate bore and
secure with the allen head screws.
CAUTION: The use of PTFE impregnated pipe
compound and PTFE tape on pipe threads
provides lubricity, which can lead to overtightening and
breakage. Do not overtighten. Failure to follow this
instruction can result in moderate personal injury and/or
property damage.
CAUTION: The generous use of pipe joint
compound when installing the adapter or P/T will
foul the valve operating mechanism preventing it from
functioning properly. Pipe joint compound must be
conservatively applied to male threads only. Failure to
follow this instruction can result in moderate personal
injury and/or property damage.
WARNING: System fluid under pressure and/or at
high temperature can be very hazardous. Before
servicing, reduce system pressure to zero or isolate the
pressure reducing from the system. Leave drain valve
open. Allow system to cool below 100ºF. Failure to follow
these instructions could result in serious personal injury
or death and property damage.
WARNING: Hot water leakage can occur from
readout valve during probe insertion and during
hookup of readout kit. Follow the instruction manual
supplied with readout probes and readout kits for safe
use. Failure to follow this instruction could result in
serious personal injury and/or property damage.
WARNING: Corrosion or leakages are indications
that the Wafer Valve may be about to cause
serious damage from leakage or rupture. It must be
periodically inspected and if noted, it must be replaced.
Failure to follow these instructions could result in serious
personal injury or death and property damage.
CAUTION: Hot uninsulated surfaces can cause
burns to the skin. Do not touch hot surfaces.
Failure to follow these instructions could result in
moderate personal injury.