Bell & Gossett V58044B Circuit Sentry Automatic Flow-Limiting Valve User Manual
Page 2

b) For soldering, use 95-5 (Tin-Antimony) solder and a
good grade of flux.
c) Use a torch with a sharp pointed flame.
d) When sweating the joints, first adjusting the
Automatic Flow-Limiting Valve in the full open
position, then wrap the valve with a cool wet rag and
then direct the flame with care to avoid subjecting
AFLV to excessive heat. Allow the valve to cool before
touching or operating.
e) Check the soldered connection for leaks.
Chart A
(SOLDER TYPE LIMITS PER ASTM STD. B16.22-1989)
OPERATING INSTRUCTIONS
Operation of the Automatic Flow-Limiting Valve is fully
automatic and does not require any adjustment. It auto-
matically maintains the selected flow over the designed
differential pressure range.
Before the system start up, remove cartridge from the valve.
Flush the hydronic system and then reassemble cartridge into
the valve and make sure cap is tightened properly. Start the
system and check for the AFLV leak.
HOW TO USE AUTOMATIC FLOW-LIMITING
VALVE PRESSURE TAPS TO DETERMINE
PROPER FUNCTIONING OF VALVE.
1.
Using Bell & Gossett Model RP-250 readout probes,
attach a Bell & Gossett differential pressure readout kit to
the readout valves on the Automatic Flow-Limiting Valve.
2.
Read the differential pressure across the Automatic Flow-
Limiting Valve. This can be compared to system pump
head to determine valve function, and system flow
blockage.
SERVICE INSTRUCTIONS
Should the Automatic Flow-Limiting Valve require cleaning or
changing the orifice, follow the following instructions.
1.
Loosen and remove the bonnet (cap) from the valve body.
2.
Pull the cartridge assembly from the valve body for
cleaning or change the new flow cartridge. Checking the
cartridge by pushing the orifice washer in to the cartridge
housing for several times to make sure spring is
functional.
3.
If you design to changing the orifice washer (for more or
less flow rate). With a screwdriver, remove the clip ring
from inside the cartridge housing. Pull the orifice washer
out and replace with the new orifice that you have
preferred.
4.
Reinstall, or replace the clip ring in the cartridge housing
groove and reassemble the bonnet with the O-ring.
WARNING: Use of improper procedures to sweat
valve model with union connection into system
can damage valve. Before installing sweat union
connection to valve, remove the union nut and O-ring
from the valve body, the union tailpiece with nut must be
sweated (soldered) into place. Failure to follow this
instruction could result in property damage and/or
moderate personal injury.
TYPE OF
MAXIMUM LIMITATIONS
SOLDER
PRESSURE PSIG
TEMPERATURE ºF
95-5
300
175
TIN-
250
200
ANTIMONY
175
250
CAUTION: Heat associated with the use of silver
solder may damage an Automatic Flow-Limiting
valve and void the product warranty. Do not use silver
solder. Failure to follow these instructions could result in
property damage and/or moderate personal injury.
CAUTION: Hot uninsulated surfaces can cause
burns to the skin. Do not touch hot surfaces.
Failure to follow these instructions could result in
moderate personal injury.
CAUTION: Hot uninsulated surfaces can cause
burns to the skin. Do not touch hot surfaces.
Failure to follow these instructions could result in
moderate personal injury.
WARNING: Hot water leakage can occur from
readout valve during probe insertion and during
hookup of readout kit. Follow the instruction manual
supplied with readout probes and readout kits for safe
use. Failure to follow this instruction could result in
serious personal injury and/or property damage.
WARNING: System fluid under pressure and/or at
high temperature can be very hazardous. Before
servicing, reduce system pressure to zero or isolate the
pressure reducing from the system. Leave drain valve
open. Allow system to cool below 100ºF (38ºC). Failure to
follow these instructions could result in serious personal
injury or death and property damage.
WARNING: Corrosion or leakages are indications
that the Automatic Flow Control Valve may be
about to cause serious damage from leakage or rupture.
It must be periodically inspected and if noted, it must be
replaced. Failure to follow these instructions could result
in serious personal injury or death and property damage.
Xylem Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. V58044B September 2012