Quick guide, Smartphone apps accessories, Chart regarding di/do extra units available soon – Xylem MY CONNECT Quick Guide User Manual
Page 2: Ce rtifie d

Order numbers:
205240 Mµ Connect
®
(w/o modem og WiFi), 6DI/2DO/3AI
205243 Mµ Connect
®
GSM/GPRS modem 6DI/2DO/3AII/O
Ekspansion modules
(max 16AI/16AO/32DI/32DO)
205260 Mµ Connect
®
I/O module 12DI
205261 Mµ Connect
®
I/O module 12DO
205262 Mµ Connect
®
I/O module 6DI/6DO
205270 Mµ Connect
®
I/O module 6AI
205271 Mµ Connect
®
I/O module 6AO
205272 Mµ Connect
®
I/O module 3AI/3AO
205280 Mµ Connect
®
I/O module 6DI/3AI
205281 Mµ Connect
®
I/O module 6DI/3AO
205282 Mµ Connect
®
I/O module 6DO/3AI
205283 Mµ Connect
®
I/O module 6DO/3AO
Accessories:
500311 DIN bus (3DIV.)
500312 DIN bus (6DIV.)
691095 PC mini USB/USB cable
840150 Instrument Link communication software
GSM/GPRS antennas read datasheet 6.26
Batteries
550240 Accumulator 12V/2Ah
550244 Accumulator 12V/1,2Ah
Connection example
Digital output
Connection example
Digital Input
NO & NC
Connection example
Analog Input
Active mA transmitter signal
Connection example:
Analog input
Passive mA transmitter signal
Expert™ 7060
+ DC Red
- DC Brown
Ground Black
GND
A
B
INET
DC
OUT
GND
15V
+1
-1
+2
AI
-2
+3
-3
NO
NC
GND
A
B
INET
DC
OUT
GND
15V
Active
4-20mA
+1
-1
+2
AI
-2
+3
-3
Transfer Relays max.:
30 VDC, l
max
200 mA
24 VAC, l
max
200 mA
iPhone
Android
SSID: MJK
Accesscode: 12345678
Change for individual code (8-18 digits/letters) via
Instrument Link™ the fi rst time you are logged on
Set up for app in Instrument Link™: ”myConnect 2P App”
MJK Automation A/S
DK: +45 45 56 06 56
NO: +47 69 20 60 70
SE: +46 53 31 77 50
NL: +31 251 672171
IRL: +353 879535625
USA: +1 847 482 8655
AUS: +61 3 9758 8533
Liability
MJK Automation A/S are liable according to the common rules of Danish
law on product liability, however, the liability is reduced to coverage of
our public liability insurance of products. To the extent where nothing
else follows in lines of invariable rules of law, we are not liable for loss of
profi ts and working defi cits or other indirect losses.
Changes
As our products are developed continuously, we reserve the right to make
any alterations without prior notice.
Specifi cations Mµ Connect
®
Power supply
11-30 V AC/DC
Power consumption
8-40 VA Depending on construction
Battery back-up
Built-in battery charger includes
surveillance of external led
accumulator, 2 - 30 Ah
Clock
Realtime clock incl. built-in lithium
battery
(exp. lifetime app. 10 years @ 20º)
Memory
32MB fl ash memory, 10x36000 logs
depending on chosen protocol
Internal communication
Modbus
®
RTU-mode
External communication
Modbus
®
RTU-mode or COMLI
®
Interface
1 pcs. RS-485 DIN bus for I/O modules
1 pcs. RS-485 galvanic separated for
instrument net
1 pcs. RS-485 galvanically separated
for Connect net
1 pcs. USB 1,1 type mini B, female
1 pcs. MMCX, female, for antenna
Specifi cations Mµ Connect
®
Enclosure
IP 20
Cabinet material
PC (Polycarbonate)
Operating conditions
-20 to 60ºC
Weight
0,5 kg
CE Approval
EN 61000-6-4:2007, EN 61000-
6-2:2005
Input and output (I/O) RTU Unit
Digital input
6 pcs. 10 - 30 V DC
Digital output
2 pcs. electronic relays (max. 24 V
AC / 30 V DC / 200 mA)
Analog input
3 pcs. Galvanically seperated, 16
bit resolution, 4-20 mA, accuracy
± 0,25 % of FS
Powersupply for I/O
1 stk. 15 V DC, 100 mA
Analog outpu
Only Mµ Connect
®
I/O module,
4 - 20 mA, Galvanically separated
Quick guide
Smartphone apps
Accessories
Bottom Back
Bottom front
01
02
03
DI
DO
C
01
02
01
02
03
DI
DO
C
01
02
Optional
8.
9.
10.
13.
14.
11.
1. Download free MJK app
2. Setup WiFi network in My
Connect
®
via Instrument Link™
3. Change code from default to
individual using Instrument Link™
4. Connect Smartphone/Tablet for WiFi
Chart regarding DI/DO extra
units available soon
CE
RTIFIE
D
IS
O 9
001-200
8
Certifi cate# 45791
Br
own
Black
Red