beautypg.com

Xylem IM064 R05 Model LB User Manual

Page 3

background image

3

1.3 Motors must be wired for proper voltage. Motor wir-

ing diagram is on motor nameplate. Wire size must
limit maximum voltage drop to 10% of nameplate
voltage at motor terminals, or motor life and pump
performance will be lowered.

1.4 Always use horsepower-rated switches, contactor and

starters.

1.5 Motor protection

1.5.1 Single-phase: Thermal protection for single-

phase units is sometimes built in (check name-
plate). If no built-in protection is provided, use
a contactor with a proper overload. Fusing is
permissible.

1.5.2 Three-phase: Provide three-leg protection with

properly sized magnetic starter and thermal
overloads.

1.6 Maximum Operating Limits:

Liquid Temperature: 140ºF (60ºC)
Working Pressure:

85 PSI

Starts per Hour:

20, evenly distributed.

1.7 Regular inspection and maintenance will increase

service life. Base schedule on operating time. Refer
to Section 8.

2. INSTALLATION

2.1 Locate pump as near liquid source as possible (below

level of liquid for automatic operation).

2.2 Protect from freezing or flooding.
2.3 Allow adequate space for servicing and ventilation.
2.4 All piping must be supported independently of the

pump, and must “line-up” naturally.

NEVER DRAW PIPING IN PLACE BY

FORCING THE PUMP SUCTION AND

DISCHARGE CONNECTIONS.

2.5 Avoid unnecessary fittings. Select sizes to keep fric-

tion losses to a minimum.

2.6 Units may be installed horizontally, inclined or verti-

cally.

DO NOT INSTALL WITH MOTOR

BELOW PUMP. ANY LEAKAGE OR

CONDENSATION WILL AFFECT THE MOTOR.

2.7 Foundation must be flat and substantial to eliminate

strain when tightening bolts. Use rubber mounts to
minimize noise and vibration.

2.8 Tighten motor hold-down bolts before connecting

piping to pump.

3. SUCTION PIPING

3.1 Low static suction lift and short, direct, suction pip-

ing is desired. Consult pump performance curve for
Net Positive Suction Head Required.

SAFETY INSTRUCTIONS

TO AVOID SERIOUS OR FATAL PERSONAL

INJURY OR MAJOR PROPERTY DAMAGE, READ

AND FOLLOW ALL SAFETY INSTRUCTIONS IN

MANUAL AND ON PUMP.
THIS MANUAL IS INTENDED TO ASSIST IN THE

INSTALLATION AND OPERATION OF THIS UNIT

AND MUST BE KEPT WITH THE PUMP.

This is a SAFETY ALERT SYMBOL.

When you see this symbol on the pump

or in the manual, look for one of the

following signal words and be alert

to the potential for personal injury or

property damage.
Warns of hazards that WILL cause

serious personal injury, death or major

property damage.
Warns of hazards that CAN cause

serious personal injury, death or major

property damage.
Warns of hazards that CAN cause per-

sonal injury or property damage.

NOTICE: INDICATES SPECIAL INSTRUCTIONS

WHICH ARE VERY IMPORTANT AND

MUST BE FOLLOWED.

THOROUGHLY REVIEW ALL INSTRUCTIONS

AND WARNINGS PRIOR TO PERFORMING ANY

WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.

UNIT NOT DESIGNED FOR USE

WITH HAZARDOUS LIQUIDS OR

FLAMMABLE GASES. THESE

FLUIDS MAY BE PRESENT IN

CONTAINMENT AREAS.

DESCRIPTION and SPECIFICATIONS:

The Model LB is a single stage, centrifugal jet pump for

general liquid transfer service and booster applications.

The liquid end utilizes a 304SS stamped casing, Noryl®

impeller, Lexan® ejector and guidevane, Amodel®

motor adapter and EPR o-rings. All motors are NEMA

48Y and 56Y square flange with a 304SS threaded shaft

extension.

1. IMPORTANT

1.1 Inspect unit for damage. Report any damage to car-

rier/dealer immediately.

1.2 Electrical supply must be a separate branch circuit

with fuses or circuit breakers, wire sizes, etc., in
compliance with National and Local electrical codes.
Install an all-leg disconnect switch near pump.

ALWAYS DISCONNECT ELECTRICAL

POWER WHEN HANDLING PUMP OR

CONTROLS.

DANGER

WARNING

CAUTION

WARNING

Hazardous fluids

can cause fire,

burns or death.

CAUTION

CAUTION

CAUTION