23

Figure 15: Entering the password for the set point

screen


This allows the user to edit the set point.
Touch the button next to the Set point value:

Figure 16: Changing the set point


Change the set point as required. Be careful not
to set the value too low for the pump you are
using, nuisance overloads can occur. Also, do not
set the value too high for your systems piping or
damage may occur.

TRENDS AND ALARMS

Press the Graph button to access the
history/performance graph. Scroll to access
historical data up to 2.3 days of data for pressure,
Flow, Set point and VFD Speed.

Figure 17: Performance Graph

Press the Alarm button to view up to 32 previous
alarms.

Figure 18: Alarms Screen

Alarms are shown as shown in figure 15 below.

Figure 19: Alarm Description