add 7/8” for mating connectors
The PM IDD 9000 is available as single or dual channel. The dual channel has
a separate, identical PCB motherboard for each channel. Each board contains
six connectors on the side panels. Dual channel shown, bottom board is re-
moved on single channel configuration.
14.00
1.75
6.50
LEFT SIDE VIEW
BACK
J1
J2
J3
J4
J5
J6
Channel 1
Channel 2
Panel Mount IDD 9000
Rack Mount IDD 9000
The RM IDD 9000 is a dual channel amplifier with a separate identical CPU
Processor for each channel. The right side is for Channel 1 and the left side
is Channel 2. The RM IDD 9000 is designed for installation into an amplifier
rack (Part # 404325-02) in an equipment cabinet.
IDD 9000 Flame Detector Amplifier
Products and Accessories:
Dual Channel Panel Mount (PM) IDD 9000 Amplifier
Part #408100-00
Single Channel Panel Mount (PM) IDD 9000 Amplifier
Part #408100-50
Rack Mount (RM) IDD 9000 Amplifier - dual channel
Part #408120-01
Amplifier Tuning Kit
Part #408103-01
Termiflex / SMARTDisplay
®
terminal with 9-pin connector*
Part #408106-01
Cable 40’ (for IDD)
Part #399854-04
Cable 40’ (for UV-4)
Part #399855-04
Compatible Flame Detectors:
IDD-II, Filtered, Infrared Detector
IDD-IIU, Unfiltered, Infrared Detector
IDD-IIL, Infrared Detector for Lignite
UV-4, UV Tube Detector
Part #38321-21
Part #38321-22
Part #38321-23
Part #379189-02
*
If using an older Termiflex / SMARTDisplay
®
terminal with a 25-pin connection, a DB25-pin to DB9-pin adapter is required (Forney Part #408107-01)
IDD 9000 Specifications:
Panel Mount:
Rack Mount:
Dimensions:
10 1/2” x 7 7/8” x 3 7/8” (26.6 cm x 20 cm x 9.8 cm)
6.5 x 14 x 1.75 inches (155.6 x 355.6 x 44.5 mm)
Weight:
5 lbs. 3 oz.
1 lb 7 oz.
Temperature:
32° to 140°F (0° to 60°C)
Humidity:
5% to 95% relative humidity, non-condensing
Power Requirements:
120/240 VAC, 50/60 Hz @ 12 VA
Output Relay Ratings (SPDT):
3 A at 125 VAC, 250 VAC & 30 VDC
3 relays are available for each channel (Lamp, Main Flame & Alarm).
Flame Strength:
4-20 mA or 0-10 VDC (sourcing)
Flame Failure Response Time (FFRT):
2.0, 3.0 or 3.8 seconds
Flame Pickup Time:
less than 2 seconds
Nonvolatile RAM:
8 complete operating profiles
Approvals:
Factory Mutual (FM)
Pub # 404005-21
Rev 11/2011
Forney Corporation • 3405 Wiley Post Road • Carrollton, TX 75006 • 800-356-7740 • Fax 972-458-6650 • www.forneycorp.com