Forney MAXFire 40 Low Pressure User Manual
Page 2

Forney Corporation
3405 Wiley Post Road
Carrollton, TX 75006 USA
Tel: 972.458.6100
Fax: 972.458.6650
www.forneycorp.com
IGNITERS
MAXFIRE SPECIFICATIONS
Fuel:
Natural gas
Fuel Pressure:
1.5 psig (0.103 bar)
Maximum Length:
10 feet (304.8 cm)
Guide Tube Material:
Carbon steel with 12 inches stainless steel at furnance end
MAXFire
CAPACITY
GUIDE TUBE COOLING AIR REQUIREMENT
TIP
MODEL
MBTU/HR OD
(ABOVE WINDBOX)
TYPE
40
6.0
4.0 inches
60 scfm @ 6 inches wc
Straight nozzle
101.6 mm
1.7 m3/min @ 14.9 mbar
For other sizes and capacities consult the factory.
HESI SPECIFICATIONS
Input Voltage:
120 to 240 VAC 50/60 HZ
Output Voltage:
2000 VDC
Output Energy:
12 joules per spark
Spark Rate:
3 per second (approx.)
Duty Cycle:
50% at – 18 to 57°C (0 to 135°F)
HTSI SPECIFICATIONS
Amperage:
20 mA
Input Voltage:
120 to 240 VAC 50/60 HZ
Output Voltage:
6000 VDC
Input Current:
1.5 A (2-A fuse); 240 VAC @ 0.75A (1-A fuse)
Duty Cycle:
100% at temperature rating
TECHNICAL BULLETIN
PUBLICATION
#404006-18
REV 06/06
MAXF
IRE
40 L
OW
P
RESSURE
G
A S
I
GNITER