Maxfire, Series 100 gas igniters – Forney MAXFire 100 User Manual
Page 2

MAXFire
®
Series 100 Gas Igniters
Specifications
Fuel:
Natural gas or propane
Minimum Length:
14 inches
Guide Tube Material:
10 & 30 - Stainless steel
35, 40 & 50 - Carbon steel with 12” stainless steel at furnace end
MAXFire
Model
Capacity
MBtu/hr
Guide
Tube OD
Connections (NPT)
Cooling Air
Requirement*
Nozzle
Type
Typical Fuel
Pressure (psig)
Gas
Air
110
0.3 to 1.5
1 7/8”
1/2”
3/4”
23 @ 3
Straight
5-12
130
1.5 to 6.0
2 7/8”
3/4”
3/4”
45 @ 3
Straight or wide
5-12
135
5.0 to 15
3 1/2”
1 1/2”
1 1/2”
50 @ 6
Straight or wide
5-25
140
5.0 to 25
4”
1 1/2”
1 1/2”
80 @ 6
Straight or wide
5-25
150
10 to 50
5”
TBD
TBD
120 @ 6
Straight or wide
5-25
*scfm@inches w.c. above windbox
HESI Specifications
Input Voltage:
120 to 240 VAC, 50/60 Hz
Input Power:
120 VAC @ 1.5 A (2-A fuse); 240 VAC @ 0.75A (1-A fuse)
Output Voltage:
2000 VDC
Output Energy:
12 joules per spark
Spark Rate:
3 per second (approximately)
Duty Cycle:
50% at temp 0°F to 135°F (-18°C to 57°C) Ambient
HTSI Specifications
Amperage:
20 mA
Input Voltage:
120 to 240 VAC 50/60 HZ
Output Voltage:
6000 VAC
Duty Cycle:
100% at temperature rating
Primary Combustion Zone
Clamp
Guide Tube
Cooling/combustion Air Inlet
Gas Inlet
HESI
Pub # 404006-19
Rev 01/2011
Forney Corporation • 3405 Wiley Post Road • Carrollton, TX 75006 • 800-356-7740 • Fax 972-458-6650 • www.forneycorp.com