beautypg.com

Specifications – PowerWalker VI 650 LCD_FR User Manual

Page 8

background image

EN

8. Specifications

Model

VI 450 LCD

VI 650 LCD

VI 850 LCD

CAPACITY

450 VA / 240 W

650 VA / 360 W

850 VA / 480 W

INPUT
Voltage

220~240 VAC

Voltage Range

162~290 VAC

Frequency Range

50/60Hz±1Hz

OUTPUT
Voltage Regulation

+/-10%

Transfer Time

Typical 2-6 ms, 10 ms max.

Waveform

Simulated Sine Wave

Protection

Short circuit and overload protection

BATTERY
Type & Number

12V / 4.5Ah x 1

12V/ 7Ah x 1

12V/ 9Ah x 1

Charging Time

4-6 hours recover to 90% capacity

Protection

Discharge and overcharge protection

Backup Time (est. 120W)

5 min

10 min

15 min

PHYSICAL
LCD Indicator

Input/output voltage, AC mode, Load level, Battery capacity

Dimension (DxWxH)

287mm x 100mm x 142mm

ENVIRONMENT
Humidity

0-90 % RH @ 0-40° C (non-condensing)

Noise Level

Less than 40 dB

Model

VI 1000 LCD

VI 1500 LCD

VI 2000 LCD

CAPACITY

1000 VA / 600 W

1500 VA / 900 W

2000 VA / 1200 W

INPUT
Voltage

220/230/240 VAC

Voltage Range

162~290 VAC

Frequency Range

50/60 Hz (Auto sensing)

OUTPUT
Voltage Regulation

+/-10%

Frequency Range

50 or 60 Hz +/-1 Hz

Transfer Time

Typical 2-6 ms, 10 ms max.

Waveform

Simulated Sine Wave

BATTERY
Type & Number

12V / 7Ah x 2

12V / 9Ah x 2

12V / 9Ah x 2

Charging Time

4-6 hours recover to 90% capacity

Protection

Overload, discharge and overcharge protection

Backup Time (est. 240W)

11 min

18 min

20 min

PHYSICAL
LCD Indicator

Input/output voltage, AC mode, Load level, Battery capacity

Dimension (DxWxH)

350x146x160 mm

397mm x 146mm x 205 mm

ENVIRONMENT
Humidity

0-90 % RH @ 0-40° C (non-condensing)

Noise Level

Less than 40 dB