Velleman HAA52N User Manual
Page 6
HAA52N
01 (10/10/2008)
6
e.
Wiring and Finishing
• Fix the PCB back onto the rear cover.
• Connect the wiring to the terminal block.
• Place the front cover onto the rear cover and fix with the screw. Make sure you hear the tamper
switch clicking. Align the detector.
8. Walk test
• Walk test can be performed after the power-up display expired - the alarm LED is flashing during
the power-up period - to test the detector over the entire protected area to verify proper
operation of the unit.
• Walk into the protected area at a rate of one step per second across the protection beams and
observe the LED.
• Alarm is triggered when the detector is tripped under standard alternate polarity signal
processing at normal condition.
• The harsh condition requires the detector to be tripped twice within ten seconds under double
alternate polarity signal processing.
9. Technical specifications
Current Consumption
15mA @ 12VDC
Operating Voltage
8 ~ 16VDC, 12VDC nominal
Detection Method
PIR with alternate polarity processing
Power-up Delay
2 minutes with flashing LED
Alarm Period
2 ~ 3s
Alarm Output
NO or NC contact with 10Ω in-line resistor
Walk Test LED
alarm indicator, enable-disable selectable
Pulse Counting
normal response or 2 pulses within 10s
Tamper Switch
NC contact with 10Ω in-line resistor
Operating Temperature
-10°C ~ 55°C
Humidity
95% non-condensing
Dimensions
105 x 60 x 42mm
Weight 82g
Use this device with original accessories only. Velleman nv cannot be held responsible in
the event of damage or injury resulted from (incorrect) use of this device.
For more info concerning this product, please visit our website www.velleman.eu.
The information in this manual is subject to change without prior notice.