4 Connecting to power supply and bus system

VEGABAR 86 • Modbus and Levelmaster protocol

46324-EN-131125

4 Connecting to power supply and bus

system

4.1 Connection

The voltage supply and signal output are connected via the spring-

loaded terminals in the housing.
Connection to the display and adjustment module or to the interface

adapter is carried out via contact pins in the housing.
Information:

The terminal block is pluggable and can be removed from the

electronics. To do this, lift the terminal block with a small screwdriver

and pull it out. When reinserting the terminal block, you should hear it

snap in.

Proceed as follows:
1. Unscrew the housing cover
2. Loosen compression nuts of the cable glands
3. Remove approx. 10 cm (4 in) of the cable mantle (signal output),

strip approx. 1 cm (0.4 in) insulation from the ends of the indi-

vidual wires

4. Insert the cable into the sensor through the cable entry

Fig. 3: Connection steps 5 and 6

5. Insert the wire ends into the terminals according to the wiring plan
Information:

Solid cores as well as flexible cores with wire end sleeves are insert-

ed directly into the terminal openings. In case of flexible cores without

end sleeves, press the terminal from above with a small screwdriver,

the terminal opening is then free. When the screwdriver is released,

the terminal closes again.

Connection technology

Connection procedure