2 parameter adjustment - quick setup – VEGA VEGABAR 87 HART and accumulator pack - Quick setup guide User Manual
Page 12
12
5 Set up with the display and adjustment module
VEGABAR 87 • HART and accumulator pack
46326-EN-131125
1
2
Fig. 7: Insertion of the display and adjustment module into the double chamber
housing
1 In the electronics compartment
2 In the connection compartment (with Ex-d-ia version not possible)
Note:
If you intend to retrofit the instrument with a display and adjustment
module for continuous measured value indication, a higher cover with
an inspection glass is required.
5.2 Parameter adjustment - Quick setup
To quickly and easily adapt the sensor to the application, select
the menu item "Quick setup" in the start graphic on the display and
adjustment module.
Carry out the following steps in the below sequence.
You can find "Extended adjustment" in the next sub-chapter.
1. Measurement loop name
In the first menu item you assign a suitable measurement loop name.
Permitted are names with max. 19 characters.
2. Application
In this menu item, you activate/deactivate the slave for the electronic
differential pressure and select the application. The application com-
prises process pressure and level measurement.
Presettings