beautypg.com

VEGA VEGAFLEX 86 4 … 20 mA_HART - four-wire User Manual

Page 32

background image

32

6 Set up with the display and adjustment module

VEGAFLEX 86 • 4 … 20 mA/HART - four-wire

41845-EN-130314

You can find "Extended adjustment" in the next sub-chapter.
Measurement loop name

In the first menu item you can assign a suitable measurement loop

name. You can enter a name with max. 19 characters.
Product type

In the next menu item you can see which product type the instrument

is suitable for. If your instrument is only suitable for a certain medium,

this menu item is not visible.
Application

In this menu item, you can select the application. You can choose

between level measurement and interface measurement. You can

also choose between measurement in a vessel or in a bypass or

standpipe.

Medium - dielectric constant

In this menu item, you can define the medium type (product).
Max. adjustment

In this menu item, you can enter the max. adjustment for the level.
Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.
Min. adjustment

In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

Dielectric constant - upper medium

In this menu item, you can define the medium type (product).
Max. adjustment

In this menu item, you can enter the max. adjustment for the level.
Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

General information

Level measurement

Interface measurement