4 Mounting
VEGASWING 51 • - contactless electronic switch
41045-EN-130322
4 Mounting
4.1 General instructions
Make sure that all parts of the instrument coming in direct contact
with the process, especially the sensor element, process seal and
process fitting, are suitable for the existing process conditions, such
as process pressure, process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data" and on the
nameplate.
Generally, VEGASWING 51 can be mounted in any position. Just
install the instrument so that the tuning fork is at the height of the
requested switching point. Keep in mind that the switching point can
vary depending on the installation position.
The switching point refers to the medium water (1 g/cm³/0.036 lbs/
in³). Please keep in mind that the switching point of the instrument
shifts when the medium has a density differing from water.
2
3
1
11 mm (0.43")
34 mm (1.34")
Fig. 2: Mounting vertical
1 Switching point
2 Switching point with lower density
3 Switching point with higher density
2
1
Fig. 3: Mounting horizontal
1 Switching point
2 Switching point (recommended mounting position, particularly for adhesive
products)
Suitability for the process
conditions
Switching point