7 Set up with the display and adjustment module

POINTRAC 31 • 8/16 mA/HART - four-wire

43388-EN-131119

Setup
Enter here, the respective application.
This menu item enables adaptation of the sensor to the requested

application. Only the application "Point level" can be selected with

your instrument.

The natural radiation on earth influences the accuracy of the meas-

urement.
With this menu item the natural background radiation can be faded

out.
For this purpose, the POINTRAC 31 measures the natural back-

ground radiation and sets the pulse rate to zero.
In the future, the pulse rate from this background radiation will be

automatically deducted from the total pulse rate. This means: only

the component of the pulse rate originating from the source will be

displayed.
The source container must be closed for this setting.

In this menu item you can select the temperature unit.

in this menu item you can select if you want to carry out a single or

double point adjustment on the sensor.
With the double point adjustment, the Delta I value is selected auto-

matically.
We recommend selecting the double point adjustment. To use this,

you must be able to change the level of the vessel so as to carry out

the adjustment of the sensor with full status (covered) and with empty

status (uncovered).
Hence, you will get a very reliable switching point.
With single point adjustment, you have to define the difference

between the min. and max. adjustment points (Delta I) yourself during

the following setup.

Setup - Application

Setup - Background

radiation

Setup/Unit

Setup - Adjustment mode