4 Mounting

VEGABAR 81 • Profibus PA

45020-EN-131107

The filter element is mounted into the electronics housing. It has the

following functions:

Ventilation electronics housing

Atmospheric pressure compensation (with relative pressure meas-

uring ranges)

The process assembly of instruments with Second Line of Defense

(gastight leadthrough) is completely encapsulated. An absolute pres-

sure measuring cell is used so that no ventilation is required.

1

1

Fig. 7: Position of the filter element - gastight leadthrough
1 Filter element

With relative pressure measuring ranges, the ambient pressure is

detected and compensated by a reference sensor in the electronics.

The filter element is mounted into the electronics housing. It has the

following functions:

Ventilation electronics housing

Atmospheric pressure compensation (with relative pressure meas-

uring ranges)

1

Fig. 8: Position of the filter element - IP 69K version
1 Filter element

Instruments with absolute pressure have a blind plug mounted

instead of the filter element.

4.3 Process pressure measurement

Keep the following in mind when setting up the measuring system:

Mount the instrument above the measuring point

Possible condensation can then drain off into the process line.

Instruments with Second

Line of Defense

Instruments in IP 69K

version

Measurement setup in

gases