5 Setup
Electronics module • VEGAFLEX series 80
43656-EN-121113
5 Setup
5.1 Setup preparations
If you have ordered the electronics module by stating the sensor
serial number, it is ready for the setup steps after installation and
connection to power supply.
If you have ordered the electronics module without stating the sen-
sor serial number or you are using a suitable electronics module
from stock, you first have to load the sensor data after installation.
Move via www.vega.com to the item "serial number search". The
order data of the sensor will be displayed after entering the serial
number.
Below the order data you will find "Sensor data for Service-DTM" as
XML file. This file includes all sensor-specific parameters as well as
the data of the factory setting.
Load this file with "Save target as" on your PC. Start PACTware and
under "Instrument data" go to the menu item "Additional functions",
then to "Electronics exchange". Transfer the XML file to the sensor.
5.2 Setup steps
If the instrument is used in the same application after the electronics
exchange, the previous parameter adjustment of the instrument must
be restored. For this purpose, you can use the import function of the
adjustment software PACTware with the device DTMs or the copy
function of the indicating and adjustment module.
Information:
It is recommended to recreated an existing false signal suppression
after an electronics exchange. If this is not possible, for example,
because the vessel is filled, the false signal suppression can be
imported also via the DTM. However, the false signal suppression
should be updated or recreated next time when the vessel is empty.
With sensor serial num-
ber
Without sensor serial
number
Parameter adjustment