20

5 Connecting to power supply

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

42284-EN-130612

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

Power supply and current signal are carried on the same two-wire

cable. The operating voltage can differ depending on the instrument

version.
The data for power supply are specified in chapter "Technical data".
Provide a reliable separation between the supply circuit and the

mains circuits according to DIN EN 61140 VDE 0140-1.
Keep in mind the following additional factors that influence the operat-

ing voltage:

Lower output voltage of the power supply unit under nominal load

(e.g. with a sensor current of 20.5 mA or 22 mA in case of fault

message)

Influence of additional instruments in the circuit (see load values in

chapter "Technical data")

The signal conditioning instruments VEGAMET and VEGASCAN

have digital sensor recognition. When connecting VEGAFLEX 86, an

up-to-date version of the signal conditioning instrument software is

required. For a software update go to "www.vega.com/downloads"

and "Software".

The instrument is connected with standard two-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326-1 for industrial areas, screened cable should

be used.
Use cable with round cross section for instruments with housing and

cable gland. To ensure the seal effect of the cable gland (IP protection

rating), find out which cable outer diameter the cable gland is suitable

for.

5 … 9 mm (0.20 … 0.35 in)

6 … 12 mm (0.24 … 0.47 in)

10 … 14 mm (0.40 … 0.55 in)

Use a cable gland fitting the cable diameter.
We generally recommend the use of screened cable for HART multi-

drop mode.

With plastic housing, the NPT cable gland or the Conduit steel tube

must be screwed without grease into the threaded insert.
Max. torque for all housings see chapter "Technical data".

Safety instructions

Voltage supply

Connection to signal con-

ditioning instruments

Connection cable

Cable gland ½ NPT