beautypg.com

VEGA VEGABAR 87 4 … 20 mA - Operating Instructions User Manual

Page 58

background image

58

11 Supplement

VEGABAR 87 • 4 … 20 mA

45507-EN-131010

0,15 %

-0,15 %

-40°C

-20°C

20°C

40°C

60°C

80°C

Fig. 26: Thermal change, current output

Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the

analogue current output 4 … 20 mA under reference conditions. The specifications refer to the set

span. Turn down (TD) is the ratio nominal measuring range/set span.
The long-term drift of the zero signal corresponds to the value F

Stab

in chapter "Calculation of the

total deviation (according to DIN 16086)".
Long-term drift of the zero signal

Time period

All measuring ranges

Measuring range

0 … +0.025 bar/0 … +2.5 kPa

One year

< 0.05 % x TD

< 0.1 % x TD

Five years

< 0.1 % x TD

< 0.2 % x TD

Ten years

< 0.2 % x TD

< 0.4 % x TD

Long-term drift of the zero signal - Version climate-compensated

Nominal measuring range in bar/kPa

Nominal measuring range

in psig

Long-term drift of the ze-

ro signal

0 … 10 bar/0 … 1000 kPa

0 … 150 psig

< (0.1 % x TD)/year

0 … 25 bar/0 … 2500 kPa

0 … 350 psig

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< (0.25 % x TD)/year

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

< (1 % x TD)/year

Ambient conditions

Version

Ambient temperature

Storage and transport temper-

ature

Version with connection tube

-40 … +80 °C (-40 … +176 °F)

-60 … +80 °C (-76 … +176 °F)

Version with suspension cable FEP -20 … +80 °C (-4 … +176 °F)

-20 … +80 °C (-4 … +176 °F)

Version IP 68 (1 bar) with connec-

tion cable PE

-20 … +60 °C (-4 … +140 °F)

-20 … +60 °C (-4 … +140 °F)