VEGA VEGABAR 87 4 … 20 mA - Operating Instructions User Manual
Page 58
58
11 Supplement
VEGABAR 87 • 4 … 20 mA
45507-EN-131010
0,15 %
-0,15 %
-40°C
-20°C
20°C
40°C
60°C
80°C
Fig. 26: Thermal change, current output
Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the
analogue current output 4 … 20 mA under reference conditions. The specifications refer to the set
span. Turn down (TD) is the ratio nominal measuring range/set span.
The long-term drift of the zero signal corresponds to the value F
Stab
in chapter "Calculation of the
total deviation (according to DIN 16086)".
Long-term drift of the zero signal
Time period
All measuring ranges
Measuring range
0 … +0.025 bar/0 … +2.5 kPa
One year
< 0.05 % x TD
< 0.1 % x TD
Five years
< 0.1 % x TD
< 0.2 % x TD
Ten years
< 0.2 % x TD
< 0.4 % x TD
Long-term drift of the zero signal - Version climate-compensated
Nominal measuring range in bar/kPa
Nominal measuring range
in psig
Long-term drift of the ze-
ro signal
0 … 10 bar/0 … 1000 kPa
0 … 150 psig
< (0.1 % x TD)/year
0 … 25 bar/0 … 2500 kPa
0 … 350 psig
0 … 1 bar/0 … 100 kPa
0 … 15 psig
< (0.25 % x TD)/year
0 … 2.5 bar/0 … 250 kPa
0 … 35 psig
0 … 0.4 bar/0 … 40 kPa
0 … 6 psig
< (1 % x TD)/year
Ambient conditions
Version
Ambient temperature
Storage and transport temper-
ature
Version with connection tube
-40 … +80 °C (-40 … +176 °F)
-60 … +80 °C (-76 … +176 °F)
Version with suspension cable FEP -20 … +80 °C (-4 … +176 °F)
-20 … +80 °C (-4 … +176 °F)
Version IP 68 (1 bar) with connec-
tion cable PE
-20 … +60 °C (-4 … +140 °F)
-20 … +60 °C (-4 … +140 °F)